00Group Basic Function - Danfoss VFD500 Series Manual

Table of Contents

Advertisement

Chapter 5 Function code
Function
Parameter name
code
P00.00
User password
P00.01
Access authority
Parameter copy and
P00.02
P00.03
P00.04
Motor Control mode
P00.05
Running mode
VFD500 high performance vector control frequency inverter user manual

00Group Basic Function

0 ~ 65535
No user password status after power-on
(P00.01=1):
The way to set a user password to lock is that
Entering the same non-zero value two tmes in
succession
Locked staus
Enter the password to unlock
Unlocked status
Enter the original password to lock inverter;
enter the same value twice in a row to change
the password (password will be cleared if you
enter 0 two times in a row).
0:END USER
Some parameter are not authorized to check
when user password in locked state
Standard
ALL Parameter can be checked
0:No action 

11:save all parameter to EEPROM backup
space
backup
12:Restore all parameter from EEPROM
backup space
0:NO ACTION
11:Restore default parameter except for
motor parameter and auto-tune related
RESET
parameter and factory parameter
12:Restore default to factory parameter
13:Clear tripping record
0:VF
1:SVC(sensorless vector control)
Open loop vector without encoder
feedback and the feedback speed is
internally estimated and supports torque
control mode.
2:VC Vector control with sensor
Close loop vec tor and torque control
supporting encoder feedback in high
precision or torque control
application.The inverter must be
equipped with a PG card that matches
the encoder. For the relevant parameters
of the PG card, please refer to P10 group
0:Speed mode
1:Torque mode
➢ If use with DI function,19:Switch between
torque and speed Control and 20: torque
control diabled. Actuall effective running
mode is related with DI status
Description
42
Default
Property
0
1
1:
0
0
0
0