VFD500 high performance vector control frequency inverter user manual
Actual output Pulse
r05.00
frequency
P05.01
HDO Pulse Output type
HDO output source
P05.02
selection
HDO Minimum output
P05.03
pulse frequency
HDO Max output pulse
P05.04
frequency
r05.05
AO1 actual value
AO1 output function signal
P05.06
selection
P05.07
AO1 output offset
P05.08
AO1 output gain
The output error of AO1 can be corrected by P05.07 and P05.08, or the mapping relationship between signal
source and actual output can be changed. The formula is:
AO.c = P05.07 + P05.08 × AO.pAO.c: the actual output of AO1;
AO.p: AO1 Value before correction and AO.c, AO.p, 100.0% of P05.07 corresponds to 10V or 20mA.
r05.09
AO2 actual value
AO2 output function signal
P05.10
selection
P05.11
AO2 output offset
P05.12
AO2 gain
The output error of AO2 can be corrected by P05.11 and P05.12, or the mapping relationship between signal
source and actual output can be changed. The formula is:
AO.c = P05.11 + P05.12 × AO.pAO.c: the actual output of AO2;
AO.p: AO2 value before correction and AO.c, AO.p, 100.0% of P05.11 corresponds to 10V or 20mA.

05 Group Analog and Pulse output

0.00kHz~50.00kHz
0:Common numeric output (DO2 P07.02)
1:high frequency pulse output (Hdo)
0:Running frequency(0~max frequency)
1:Set frequency(0~max frequency)
2:output current(0~2times motor rated
current)
3:output torque(0~3times motor rated torque)
4:set torque(0~3times motor rated torque)
5:output voltage(0~2times motor rated
voltage)
6: DC bus voltage(0~2times drives standard
DC bus voltage)
7: output power(0~2times motor rated
power)
8:encoder rotating speed(0-maximum frequency
rotating speed)
9: AI1(0.00~10.00V)
10: AI2(0.00~10.00V)
11: AI3(0.00~10.00V)
12: AI4(0.00~10.00V)
0.00kHz~50.00kHz
HDO terminal output pulse frequencywhen
Output signal source=0
0.00kHz~50.00kHz
HDO terminal output pulse frequencywhen
Output signal source=maximum value
0.0%~100.0%
Same as P05.02 function description
-100.0%~100.0%
-10.00~10.00
0.0%~100.0%
Same as P05.02 function description
-100.0%~100.0%
-10.00~10.00
59
Chapter 5 function code table
-
0
0
1.00kHz
30.00kHz
-
0
0.0%
1.00
-
0
0.0%
1.00