Chapter 6 Fault diagnosis and solutions
Fault Name
PID feedback
lost during
running
User-defined
fault 1
User-defined
fault 2
!
The fault code is used for the communication read fault type: when the communication reads
the registers r25.00, r26.00, r26.08, r26.16, the register contents of the reply are fault coded.

6.2 Warning type

The warning is used to remind and inform the user of the current state of the inverter. When the warning
occurs, the keypad will display a warning message, and the warning will automatically reset when the
warning is cleared. Some warnings require the user to check the cause before running the drive, and
some do not care. Warning As an instant reminder, the drive does not store the corresponding
information.
Bit 12 of r27.10 indicates whether there is a warning message currently.
War
Warning
nin
name
g
cod
Insufficient
1
power
Wrong
2
parameter
Sleeping
5
status
!
The warning code is used for the communication read warning type: when the communication
reads register r25.16, the contents of the returned register are the warning code.
VFD500 high performance vector control frequency inverter user manual
Faul
Disp
t
lay
cod
e
1. PID feedback<P40.35
Er.F
setting value and P40.36 not
36
bL
zero,PID feedback>P40.37
setting value and P40.38 not
1: The signal of user-defined
fault 1 is
Er.U
input via DI.
37
d1
2:The signal of user-defined fault
1 is
input via virtual I/O.
1: The signal of user-defined
Er.U
fault 2 is
38
d2
input via DI.
2:The signal of user-defined fault
2 is
input via virtual I/O.
Displa
y
PoFF
1 : T h e D C l i n k v o l t a g e i s
insufficient and cannot be
started normally.
1: The parameter settings are
A.PAR
wrong, such as:
A
The torque mode is set in the
VF control mode.
1. The system is in a sleep state,
SLEE
a n d t h e s y s t e m w i l l
P
a u t o m a t i c a l l y s t a r t w h e n
hibernation is over.
Possible Causes
Reason
117
Solutions
1. Check PID feedback
signal
2. P40.35 and P40.37
set correct parameter
1: Reset the operation.
2: Reset the operation
1: Reset the operation.
2: Reset the operation
Measure
1:Check if the inverter power
supply is normal.
1:Modify and check the
parameter compatibility
problem
1:Generally no need to pay
attention to it