Group Digital Output Setting - Danfoss VFD500 Series Manual

Table of Contents

Advertisement

Chapter 5 Function code
Frequency detection value
P08.00
(FDT1)
Frequency detection
P08.01
hysteresis 1
Frequency detection value
P08.02
2(FDT2)
Frequency detection
P08.03
hysteresis 2
FDT is used to check inverter output frequency,when output frequency is greater than frequency detection
value,FDT effective,when output frequency is less than frequency detection value*(1- Frequency detection
hysteresis),FDT ineffective;whenoutput frequency is between the above two,FDT output keep no
change,following is FDT chart
Detection range of
P08.04
frequency arrival
Desired frequency attained
P08.05
Any frequency reaching
P08.06
detection amplitude 1
Desired frequency
P08.07
attained2
Any frequency reaching
P08.08
detection amplitude 2
VFD500 high performance vector control frequency inverter user manual

08 Group Digital output setting

0.00Hz~maximum frequency(P01.06)
0.0%~100.0% FDT1
0.00Hz~maximum frequency(P01.06)
0.0%~100.0% FDT2(P08.02)
Output
frequency
P08.00
FDT
suatus
invalid
0.0%~100.0% maximum frequency (P01.06)
When output frequency is between command
frequency ±P08.04*P01.06,corresponding DO
output effective signal
!
0.00Hz~maximum frequency (P01.06)
1
0.0%~100.0% maximum frequency (P01.06)
0.00Hz~maximum frequency(P01.06)
0.0%~100.0% maximum frequency (P01.06)
P08.00×P08.01
time
valid
invalid
time
66
50.00Hz
5.0%
50.00Hz
5.0%
3.0%
50.00Hz
3.0%
50.00Hz
3.0%