Chapter 5 Function code
P22.06
PWM modulation method
P22.07
DPWM switching point
P22.08
Modulating limit
P22.10
AVR function
P22.11
Energy braking voltage funtion
P22.12
Energy braking voltage
P22.13
Output phase switch
Cooling method (fan
P22.14
control)
P22.15
G/P drive type
r22.16
Drive rated power
r22.17
Drive rated Voltage
r22.18
Drive rated current
P22.20
Trial time setting
VFD500 high performance vector control frequency inverter user manual
0:SVPWM
It is normally used
1:SVPWM+DPWM
Using this modulation method can reduce the
switching loss of the inverter and reduce the
probability of overheating alarm of the
inverter; however, the electromagnetic noise
of the motor in the medium speed section will
be too large.
2:PWM at random
The electromagnetic noise generated by the
motor is white noise, not a sharp squeak.
3:SPWM
It is only used in special situation
10%~100%(modulation percentage)
When P22.06 is set to 1, increasing this
setting vaule can reduce the electromagnetic
noise in the middle speed section.
50%~110%
It is used to define the duty cycle of the
inverter side IGBT. Overmodulation is allowed
when it is set to 100% or more, and the
allowable overmodulation is deepened when
the set value is increased from 101 to 110.
0:diabled
1:enabled
When the AVR function is enabled, the effect
of the DC bus voltage change on the output
voltage can be eliminated.
0-Disabled

1-Enabled

2-only enable when ramp to stop
This parameter is only used to control the
built-in brake unit. For models without a built-
in brake unit, this setting can be ignored.
320V~400V(220V level )

600V~800V(380V level )

690V~900V(480V level )

950V~1250V(690V level)
0:No Operation

1:Output phase switch
(equal to change Phase between V and W,For
closed loop control, you need to re-rotate the
self-learning to confirm the encoder direction)
0:Effective when running

1:Forced control( effective when power on) 

2:Adjustable as per drive temperature
0-G type;1-P type
G means normal duty (constant torque
load)
P means light duty such as fan and
pump
Read only Unit:0.1kw
Read only Unit:V
Read only Unit:0.1A
After this time, the inverter will stop and report
Er.TTA fault; if set to 0, it will be cancelled.
Note: This parameter needs agency authority
to be able to see
84
0
30%
105%
1
1
Depend
0
0
0
-
-
-
0