Chapter 5 Function code
P06.22
DI1 ineffective delay time
P06.23
DI2 Effective delay time
P06.24
DI2 ineffective delay time
P06.25
DI3 Effective delay time
P06.26
DI3 ineffective delay time
P06.27
DI4 Effective delay time
P06.28
DI4 ineffective delay time
Two wire/3wire operation
P06.29
control
SB2
SB1
SB3
Two-line mode 1:
K1 is closed, the drive is running forward, K2 closed reverse operation, K1, K2 at the same time closed or
disconnected, the inverter stops running.
Two-line mode 2:
In K1 closed state, K2 disconnect the inverter forward, K2 closed inverter reverse; K1 off the inverter to stop
running.
Three-line mode 1:
DI3 is set to three-wire control function. When the SB1 button is closed, press the SB2 button. The inverter is
forward running. Press the SB3 button to invert the inverter. When the SB1 button is off, the inverter will stop.
During normal start-up and running, it is necessary to keep the SB1 button closed, and the commands of SB2
and SB3 buttons take effect during the closing operation. The running status of the inverter takes the last key
action of the three buttons as the standard.
Three-line mode 2:
DI3 is set to three-wire control function. When the SB1 button is closed, press the SB2 button to run the inverter,
K to switch the inverter forward, K to close the inverter and SB1 to turn off the inverter. During normal start-up
and operation, it is necessary to keep the SB1 button closed and the command of the SB2 button effective
during the closing operation.
VFD500 high performance vector control frequency inverter user manual
0.000s~30.000s
0.000s~30.000s
0.000s~30.000s
0.000s~30.000s
0.000s~30.000s
0.000s~30.000s
0.000s~30.000s
0:2-wire mode (FWD+REV)1
1:2-wire mode RUN+DIRECTION)2
2:3-wire 1(FWD+REV+ENABLE)
3:3-wire 2 RUN +FWD/REV+ENABLE
K1
DI1 Forward
Run (FWD)
K2
DI2 Reverse
RUN (REV)
COM
Two-line mode
Figure1:
DI1
forward
command
DI3
operation
command
DI2
reverse
command
COM
Three-line mode
Figure 3:
K1
DI1 operation
function
K2
DI2 operation
direction
COM
Two-line mode
1
Figure 2:
DI1
forward
SB2
command
DI3
stop
SB1
command
DI2 operation
K
direction
COM
-line mode
1
Figure 4:Three
62