VFD500 high performance vector control frequency inverter user manual
Function
Parameter name
code
This function is mostly used in textile and chemical industry and some application such as traversing and winding
so it is used for balancing the workload allocation when multiple motors are used to drive the same load. The
output frequency of the frequency inverters decreases as the load increases. You can reduce the workload of the
motor under load by decreasing the output frequency for this motor, implementing workload balancing among
multiple motors.P01.44 or P01.46=0,This function disable
Output frequency
Frequency
swing limit
Frequency
swing center
Frequency swing
lower limit
Start acceleration
Running
command
Auxiliary frequency
P01.48
effective threshold
Description
Frequency swing range :AW-set the frequency (choose
P01.43)*P01.44 Kick-hop frequency :jw-aw*P01.45
Jw
Jw
Triangle wave rise time :
P01.47*frequency swing
cycle
Frequency swing
cycle (P01.46)
When the main frequency ≥ this setting, the
auxiliary frequency will be effective
49
Chapter 5 function code table
Default
Property
+A
w
-Aw
Deceleration stop
0.00Hz