Chapter 5 Function code
Function
Parameter name
code
Main frequency
P01.00
source selection (A)
Auxiliary frequency
P01.01
source selection (B)
Reference option for
P01.02
auxiliary frequency
source
Auxiliary frequency
P01.03
gains
Frequency source
P01.04
selection
Main and Auxiliary
P01.05
arithmetic
P01.06
Maximum frequency
Upper limit frequency
P01.07
control
P01.08
Upper limit frequency
P01.09
Lower limit frequency
VFD500 high performance vector control frequency inverter user manual
Description
0:Digital setting
1:AI1
2:AI2
3:AI3(IO externsion card)
4:AI4(IO externsion card)
5:HDI
6:multi-step speed
7:communication
8:PID
9:Internal PLC
Notice:DI terminal function code 26-32 superior
than this function code
Same as P01.00
Notice:DI terminal function code 33 superior
than this function code
0:Relative to Maximum frequency 

1:Relative to main frequency
0.0~300.0
0:main frequency sourceA
1:auxiliary frequency sourceB
2:Main and auxiliary arithmetic results

3:Switchover between main and auxiliary
frequency 

4:switchover between main frequency source
A and A+B Arithmetic results 

5:Switchover between B and (A+B)
(*)DI function code 25 effective to
corresponding terminal ,frequency will adopt
the latter
0:A+B

1:A-B

2:The bigger of main A and Auxliary B

3:The smaller of Main A and Auxiliary B
4:A*B
A*B have better frequency adjustment ,wiely
used for winding industry, fine sand machine,
and leather, paper industry...
10.00~600.00Hz
0:digital setting (set through P01.08)

1:AI1

2:AI2

3:Reserved

4:Reserved

5:Pulse setting HDI

6:Reserved

7:Communication setting
Lower limit frequency(P01.09)~maximum
frequency (P01.06)
0.00Hz~upper limit frequency
44
Default
Property
0
0
0
100.0%
0
0
50.00Hz
0
50.00Hz
0.00Hz