VFD500 high performance vector control frequency inverter user manual
Maincontrol
function
Keypad
Communicatio
PG card
Input terminal
Function
Output terminal
Refer to Chapter 6 "Troubleshooting and Countermeasures" for the protection
Protection
function
Installation
location
Altitude
Environme
Ambient
nt
temperature
Humidity
Vibration
Storage
temperature
Installation
Others
Protection level IP20
cooling method Forced air cooling
Jog control, droop control, up to 16-speed operation, dangerous
speed avoidance, swing frequency operation, acceleration and
deceleration time switching, VF separation, over excitation
braking, process PID control, sleep and wake-up function, built-in
simple PLC logic, virtual Input and output terminals, built-in delay
unit, built-in comparison unit and logic unit, parameter backup
and recovery, perfect fault record,fault reset, two groups of motor
parametersfreeswitching, software swap output wiring, terminals
UP / DOWN
LED Digital keyboard and LCD keypad(option)
Standard:
MODBUS communication
n
CAN OPEN AND PROFINET( IN DEVELOPMENT)
Incremental Encoder Interface Card (Differential Output and
Open Collector), Rotary transformer Card
Standard:
5 digital input terminals, one of which supports high-speed pulse
input up to 50kHz;
2 analog input terminals, support 0 ~ 10V voltage input or 0 ~
20mA current input;
Option card:
4 digital input terminals
2 analog input terminals.support-10V-+10V voltage input
standard:
1 digital output terminal;
1 high-speed pulse output terminal (open collector type), support
0 ~ 50kHz square wave signal output;
1 relay output terminal(second relay is an option )
2 analog output terminals, support 0 ~ 20mA current output or 0 ~
10V voltage output;
Option card: 4 digital output terminals
Indoor, no direct sunlight, dust, corrosive gas, combustible gas,
oil smoke, vapor, drip or salt.
0-3000m.inverter will be derated if altitude higher than1000m
and rated output current will reduce by 1% if altitude increase by
100m
-10°C~ +40°C,maximum 50°C (derated if the ambient
temperature is between 40°C and 50°C)Rated output current
decrease by 1.5% if temperature increase by 1°C
Less than 95%RH, without condensing
Less than 5.9 m/s
-20°C ~ +60°C
Wall-mounted, floor-controlled cabinet, transmural
Chapter2 production information
(0.6 g)