VFD500 high performance vector control frequency inverter user manual
Fault Name
Over current
at constant
speed
Overvoltage
during
acceleration
Overvoltage
during
deceleration
Overvoltage
at constant
speed
Faul
Disp
t
lay
cod
e
1: The output circuit is grounded
or
short circuited.
2: Motor auto-tuning is
Er.O
notperformed.
4
C3
3: The voltage is too low.
4: A sudden load is added during
operation.
5: The frequency inverter model
is of
1:The input voltage is too high
2:The surge voltage is mixed in
the input power supply.
Er.O
3: There is an external force to
5
U1
drive the motor to run, or the
brake type load is too heavy
4:The acceleration time is too
short
5:The motor is shorted to ground
1:The input voltage is too high
2:The surge voltage is mixed in
the input power supply.
Er.O
3: there is an external force to
6
U2
drive the motor to run, or the
brake type load is too heavy
4:the decceleration time is too
short
5:the motor is shorted to ground
1:The input voltage is too high
2:The surge voltage is mixed in
the input power supply.
Er.O
3: There is an external force to
7
U3
drive the motor to run, or the
brake type load is too heavy
4:The acceleration or
decceleration time is too short
5:The motor is shorted to ground
Chapter6 Fault diagnosis and solutions
Possible Causes
112
Solutions
1:Eliminate external
faults.
2: Perform the motor
auto-tuning.
3:Adjust The voltage to
normal range.
4: Remove the
addedload.
5: Select a frequency
Inverter of higher power
1:The power supply
voltage is reduced to the
normal range
2:Install DC reactor
3:Cancel the external
force of the draggable
motor or install the brake
unit
4: Increase the
acceleration time
5:Eliminate the part of the
ground short circuit
1:the power supply
voltage is reduced to the
normal range
2:install DC reactor
3:Cancel the external
force of the draggable
motor or install the brake
unit
4: increase the
decceleration time
5:eliminate the part of the
ground
1:the power supply
voltage is reduced to the
normal range
2:install DC reactor
3:Cancel the external
force of the draggable
motor or install the brake
unit
4: increase the
acceleration or
decceleration time