Danfoss VFD500 Series Manual page 33

Table of Contents

Advertisement

VFD500 high performance vector control frequency inverter user manual
Terminal
Type
Symbol
+24V
Switch input
COM
DI1~DI4
Switch
output
HDO
Relay
T1A/T1B/
output 1
Relay
output2
T2BT2C
(optional)
485+
485 port
Terminal
Name
+24V current
Digital input
PLC
terminal
common
+24V ground Internal isolation from GND
Digital input
terminal 1~4
Digital input
terminal /
HDI
High-speed
pulse input
Open
DO1
collector
output
Open
collector
output /High-
speed pulse
output
Relay output
T1C
T2A/
Relay output
485 Positive
differential
signal
Chapter3 Product appearance and wiring
Terminal function description
To provide 24V power supply, generally used as a
digital input and output terminal power supply and
external sensor power
The factory default setting is connected PLC with
+24V
Terminal for on-off input high and low level switch
When using the external signal to drive DI1~DI5, it
will disconnect the connector slip of PLC with the
+24V
Optocoupler isolation, compatible with bipolar input
Frequency range:0~200Hz
Voltage range:10V~30V
Digital input terminal:same as DI1~DI4
Pulse input frequency input:0~50KHz
Voltage range:10V~30V
Optocoupler isolation
Voltage range:0V~24V
Current range:0mA ~50mA
Open collector output:same as DO1
High-speed pulse output:0~50KHz
T1A-T1B:nomal close
T1A-T1C:nomal open
Contact rating:AC 250V,3A;DC 30V,1A
T2A-T2B:nomal close
T2A-T2C:nomal open
Contact rating:AC 250V,3A;DC 30V,1A
Baud rate:
1200/2400/4800/9600/19200/38400/57600/115200b
30

Advertisement

Table of Contents
loading

Table of Contents