Information on actuator selection
Table 14: Technical data – Information on actuator selection
Delay time hardware
from 0 to 1 (0 – 90 %)
from 1 to 0 (0 – 90 %)
Rise time
from 0 to 1
Fall time
from 1 to 0
Cable length, unshielded
Resistance to recovery
Type of load
Switching frequency
Recommended minimum load
Parallel connection of 2 outputs
Type of protective circuit
Output resistance
*
Wrong diagnostics may occur at high switching frequencies with reduced load.
3.7.8
Operating state influence on output
Table 15: Technical data – Operating state influence on output
PLC CPU stop
Interruption of field bus
Interruption of S-BUS
Supply voltage under rated voltage
tolerance
Interruption of supply voltage
Output operation
Overload behavior
3.7.9
Counter 1 and 2 (configurable)
Table 16: Technical data – Counter 1 and 2 (configurable)
Event counter/Gate time measurement/pulse duration counter
Number (configurable)
Waveform
Counting depth
Counting/switching frequency
767-5803 8DIO 24V DC 0,5A (8xM12)
Typically 70 µs (resistive load)
Typically 180 µs (resistive load)
Typically 40 µs (resistive load)
Typically 40 µs (resistive load)
≤ 30 m
≤ 0,5 A (error: 1 channel)
Inductive, resistive loads and lamps
Inductive load, approx. 20 Hz
Resistive load, approx. 500 Hz
Lamp load, approx. 500 Hz
*
50 mA
For power boost
for redundant actuation of a load
External protection (e.g., recovery diodes)
< 0.4 Ω
Acc. to substitute value strategy
Acc. to substitute value strategy
0 V status
0 V status
0 V status
Non-latching
Automatic restart
2
Rectangular pulses
16 bits
0 Hz ... 1 kHz
(depending on the S-BUS cycle)
WAGO-SPEEDWAY 767