7.2.5

"DIO Module with Counter" Mode

Table 35: Overview of adjustable counter parameters for the DIO Module

Parameter
Counter value
Counter mode
Peak time basis
Gate input
State Gate
Up/down select input
Counter direction
Allow counter overwrap By default, the counter stops if the maximum value 65535 (count direction
Manual
Version 1.1.0
Description
This field indicates the counter status
The counter can be used in 3 modes:
Event counter:
The counter counts the detected pulse on the counter input.
Gate time counter:
The counter counts the pulse detected within the adjustable gate time on
the counter input
Pulse duration counter:
The counter determines the pulse duration of the pending pulses in ms.
In "Gate time counter" mode, you define the gate time:
1 ms
10 ms
100 ms
1 s
10 s
Select here whether the counter should be controlled by the module inputs
or by the process data:
Digital input
If you select this option, the counter is controlled by the module inputs
(see section "Control of the Counter via Inputs and Outputs").
No*
If you select this option, the counter is controlled by the process data
(control byte). See section "Control Byte".
The checkbox displays the current status of the gate function. If the
checkbox is activated, the counter is released.
Select here whether the count direction should be controlled by the
module inputs or by the process data:
Digital input
If you select this option, the count direction is controlled by the inputs
(see section "Control of the Counter via Inputs and Outputs").
No*
If you select this option, the count direction is controlled by the process
data (control byte). See section, "Control Byte ".
Display of the current count direction of the counter or selecting the count
direction with process data control:
- Forward (0)
- Backward (1)
forward) or 0 (count direction backward) is reached. If this function is
disabled, the counter restarts at 0 or 65535.
Parameterizing
61