Information On Selecting The Actuator; Influence Of Operating States On Output; Table 12: Technical Data - Information On Selecting The Actuator; Table 13: Technical Data - Influence Of Operating States On Output - WAGO -SPEEDWAY 767 Manual

8do 24v dc 2.0a if (4xm12) digital output module 24 v dc / 2.0 a
Hide thumbs Also See for WAGO-SPEEDWAY 767:
Table of Contents

Advertisement

WAGO-SPEEDWAY 767
767-4804/000-800 8DO 24V DC 2.0A IF (4xM12)
3.7.5

Information on Selecting the Actuator

Table 12: Technical data – Information on Selecting the Actuator
Delay time HW
from 0 to 1 (0 – 90 %)
from 1 to 0 (0 – 90 %)
Rise time
from 0 to 1
Fall time
from 1 to 0
Cable length, unshielded
Protection against reverse voltages
Type of load
Switching frequency
Recommended minimum load
Parallel connection of 2 outputs
Type of protective circuit
Output resistance
*
Wrong diagnostics may occur at high switching frequencies with reduced load.
3.7.6

Influence of Operating States on Output

Table 13: Technical data – Influence of Operating States on Output
CPU stop of PLC
Break of field bus
Break of S-BUS
Supply voltage under rated voltage
tolerance
Interruption of supply voltage
Output operation
Overload behavior
Manual
Version 1.1.0
Device Description
Typically 75 µs (resistive load)
Typically 265 µs (resistive load)
Typically 30 µs (resistive load)
Typically 50 µs (resistive load)
≤ 30 m
≤ 2 A
Inductive, resistive loads and lamps
Inductive load, approx. 20 Hz
Resistive load, approx. 500 Hz
Lamp load, approx. 500 Hz
*
50 mA
For power boost
For redundant actuation of a load
External protection (e.g., recovery diodes)
Maximum 0.1 Ω
Acc. to substitute value strategy
Acc. to substitute value strategy
0 V status
0 V status
0 V status
Non-latching
Automatic restart
25

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

767-4804/000-800

Table of Contents