Specifications - SMC Networks EX600-SDN Series Operation Manual

Fieldbus system devicenet compatible
Hide thumbs Also See for EX600-SDN Series:
Table of Contents

Advertisement

Specifications

Model
Input type
Input connector
Input channels
Sensor supplied voltage
Maximum sensor supplied
voltage
Protection
Input signal
range
Max. input signal
Input impedance
Linearity
Repeatability
Absolute accuracy
Current consumption
Display
Enclosure
Operating temp. range
Operating humidity range
Withstand voltage
Insulation resistance
Vibration resistance
Impact resistance
Standard
Weight
Voltage input
24 VDC (Supplied from power supply for control and input)
12 bit
resolution
16 bit
-10 ~ +10 V (factory default setting)
resolution
Max. ±0.5 %F.S.
(analogue input exceeds measurement range or user setting range)
500 VAC for 1 minute between external terminals and FE
500 VDC, Min. 10 MΩ between external terminals and FE
for 2 hours in each direction of X, Y and Z direction (during
2
147 m/s
EX600-AXA
M12 (5 pin), socket
2 channel (1channel/connector)
0.5 A/channel
Short circuit protection
0 ~ 10 V
1 ~ 5 V
0 ~ 5 V
-5 ~ +5 V
±15 V
100 kΩ
Max. ±0.05 %F.S
Max. ±0.15 %F.S.
Max. 70 mA
Green LED on (when input is ON)
Red LED on (Short circuit at sensor power supply)
Red LED flashing
IP67 (manifold assembly)
-10 ~ 50
35 ~ 85 %RH (no dew condensation)
10 ~ 57 Hz with constant amplitude of 0.75 mm p-p
57 ~ 150 Hz with constant acceleration of 49 m/s
de-energizing)
3 times in each direction of X, Y and Z (during de-energizing)
CE marking, UL recognition (CSA)
- 36 -
Current input
0 ~ 20 mA
4 ~ 20 mA
-20 ~ +20 mA
±40 mA
50 Ω
Max. ±0.6 %F.S.
o
C
290 g
2
No.EX##-OML0007

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EX600-SDN Series and is the answer not in the manual?

Questions and answers

Table of Contents