Atmospheric Conditions; Pollution Degree; Noise Pollution; Ventilation - Ingeteam Ingecon Sun Lite Series Installation Manual

Table of Contents

Advertisement

Manual de instalación
Installation Manual
INGECON® SUN LITE
INGECON® SUN LITE
AAY2000IKH01
AAY2000IKI01

2.1.4 Atmospheric conditions

The ambient air must be clean and relative humidity must not exceed 50% at over 40ºC. Higher levels of relative
humidity, up to 95%, can be tolerated at below 30ºC.
It should be borne in mind that moderate condensation may occasionally occur as a consequence of temperature
variations and, apart from the unit's own protection, vigilance of these units is necessary once they have been
started up on sites where it is suspected that the conditions described above will not be present.

2.1.5 Pollution degree

CATÁLOGOS
The pollution degree for which the units have been designed is level 3.
Ingecon

2.1.6 Noise pollution

When on, the inverter generates a slight buzzing sound.
PC00ISA01_A
Do not place it in an occupied room, or on light supports which might amplify this
buzz. The mounting surface must be firm and appropriate for the weight of the unit.

2.1.7 Ventilation

MANUALES
Manual de Usuario Ingecon
AAY2000IKE01
Manual de Instalación Ingecon
LITE TL
AAY2000IKH01
INGECON SUN 2.5 TL, INGECON SUN 3T L and
INGECON SUN 2.5 units are cooled correctly by
Manual de Instalación de los Accesorios de Comunicación
means of natural convection:
AAX2002IKH01
INGECON SUN 3.3 TL, INGECON SUN 3.3,
INGECON SUN 3.68 TL units are cooled correctly
with support from a single fan:
AAY2000IKI01
AAY2000IKH01
Rev. _B
Rev. _B
Date: March 2011
Fecha: Marzo 2011
DOCUMENTACIÓN RELACIONADA
®
Sun Catálogo Comercial
A zone of 30 cm above the unit and 20 cm below and at the sides
®
Sun LITE
must be left free of obstacles. Only in this way will the unit's cooling
system be able to operate correctly
The cooling system designed for the unit varies from one unit to
another as greater heating occurs at higher power and this requires
greater air flow to cool it. This is why some models are cooled by
means of natural convection and others using forced convection
with one or two fans:
LITE
®
Sun LITE
Page 13
Page 3
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents