4.5.3 Handling tasks

aquellos que resulten de derechos de patentes o registro del diseño.
All those tasks which are neither Inspection or Control will be considered to be Handling.
La correspondencia del contenido del documento con el hardware ha sido comprobada. Sin embargo,
pueden existir discrepancias. No se asume ninguna responsabilidad por la concordancia total. La infor-
Opening system: The cover is opened and closed using a system requiring tools to
mación que contiene este documento es revisada regularmente y es posible que se produzcan cambios
remove it (fasteners).
en siguientes ediciones.
El presente documento es susceptible de ser cambiado.
To carry out handling on the unit, the voltage must be disconnected.
To disconnect the voltage it is necessary to:
I. Stop the unit
II. Disconnect the PV-DC power cable, isolate it, sign it and protect it.
III. Disconnect the grid AC power cable.
IV. Wait 10 minutes for the internal capacitances to discharge, the hot parts to cool and the fan blades to
stop turning.
The copy, distribution or use of this document or of its content requires written authorisation. Any
V. Open the door and discharge the Vbus by means of a suitable discharge resistance between the
breach thereof will be reported for damages. All rights reserved including those of patent rights or
+VBUS and -VBUS.
Check there is no voltage.
design registration.
To carry out steps II, III, IV and V, it will be necessary to use the PPE stated in the section on PPE in this
The conformity of the document content with the hardware described has been checked. However,
document for work with live parts.
discrepancies may exist. Liability will not be assumed for total concordance. The information contained
in this document is regularly revised and it is possible that there may be changes in subsequent
editions.Other functions may be available which are not covered by this document.
Any work carried out which implies a modification of the original electrical settings
must be proposed to and accepted by INGETEAM.
This document may be changed.
Safety measures: Accessing the housing through any other cubicle other than that
described is strictly prohibited.
Page 26
Page 2
26
Manual de instalación
Installation Manual
INGECON® SUN LITE
INGECON® SUN LITE
AAY2000IKH01
AAY2000IKI01
AAY2000IKH01
AAY2000IKI01
Rev. _B
Rev. _B
Fecha: Marzo 2011
Date: March 2011

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents