Ingeteam Ingecon Sun Lite Series Installation Manual page 47

Table of Contents

Advertisement

Manual de instalación
Installation Manual
INGECON® SUN LITE
INGECON® SUN LITE
AAY2000IKH01
AAY2000IKI01
Screen 2.
Vdc: Voltage supplied by solar panels to the inverter.
Idc: Current supplied by solar panels to the inverter.
Screen 3.
Alarms: Status of inverter alarms. The meaning of the alarms is listed below:
0000H, No alarms.
0001H, Insufficient input voltage.
0002H, Grid frequency out of range.
0004H, Grid voltage out of range.
0008H, Overcurrent in the inverter bridge.
CATÁLOGOS
0010H, Overcurrent in the DC/DC converter.
0020H, Insulation fault.
Ingecon
0040H, Grid overcurrent.
0080H, Overtemperature
0100H, Bus overvoltage
0200H, Configuration change
PC00ISA01_A
0400H, Manual stop.
0800H, HW error
1000H, Instantaneous grid overcurrent.
2000H, Detection of island mode operation
8000H, Hardware fault alert.
The value displayed in "Inv Alarm" can be the result of the (hexadecimal) sum of two or more of the values listed
above.
E.g.: Inv Alarm = 0006H means that: The Grid Frequency and Voltage are out of range.
InvNum: Number allocated to the inverter through the menu accessible in the display.
MANUALES
Cod1: Unit operating code. This can be requested from Ingeteam's customer services.
Cod2: Unit operating code. This can be requested from Ingeteam's customer services.
Manual de Usuario Ingecon
SN: Serial Number.
Screen 4.
AAY2000IKE01
TotE: Total energy in kWh delivered by the inverter to the grid from the date it was manufactured. Recording the
serial number of the equipment marks the start of this power log.
T.Con: Number of hours the inverter has been connected to the grid.
Manual de Instalación Ingecon
Num.Con: Number of grid connections made during all hours of operation.
Screen 5.
AAY2000IKH01
ParE: Total energy in kWh delivered by the inverter to the grid since the last time the counter was reset.
Tp Con Number of hours the inverter has been connected to the grid since the counter was last reset.
Npcon: Number of grid connections since counter was last reset.
Manual de Instalación de los Accesorios de Comunicación
Screen 6.
AAX2002IKH01
FW Ver.: Unit firmware version.
DFWVer.: Unit display firmware version.
D. Boot: Version of the display program enabling firmware housing.