Atmospheric Conditions; Ventilation - Ingeteam Ingecon Sun Smart U Installation And Operation Manual

Table of Contents

Advertisement

Installation and Operation Manual
INGECON®SUN SMART U
AAS2000IKI05

2.1.4 Atmospheric conditions

2.1.5 Ventilation

STOP
AAS2000IKI05
Rev. _
Date: February 2011
The surrounding air should be clean and the relative humidity should not
exceed 50%, at more than +104ºF (+40ºC). Higher percentages of relative
humidity, up to 95%, are tolerable at temperatures below +86ºF (+30ºC).
Account should be taken of the fact that, occasionally, moderate conden-
sation may occur as a result of temperature variations. For this reason,
in addition to the inverter's own protection system, the equipment should
also be monitored when operating at sites which may not come within the
atmospheric conditions described above.
When condensation is present, never power up the equipment.
There must be a 8 in (20.3 cm) clearance at the sides and front of the
equipment, to promote the free circulation of air through the grids.
Facilitate the circulation of incoming air through the vents and through
the lower pit, if present, and also the outgoing air through the upper
vents.
It is forbidden to leave objects on the equipment.
The fans move an air flow of 674m
environment of the equipment to make sure a correct cooling.
/h that has to be available in the
3
Page 23

Advertisement

Table of Contents
loading

Table of Contents