Back-Up Operation At Sensor Malfunction - Daikin LXE10E-A Service Manual

Marine type container refrigeration unit
Table of Contents

Advertisement

https://daikin-p.ru

3.4.2 Back-up operation at sensor malfunction

Sensor malfunction
SS
Supply air temperature
sensor
RS
Return air temperature
sensor
AMBS Ambient temperature sensor All modes Continuous operation
DCHS Discharge gas
temperature sensor
EIS
Evaporator inlet
temperature sensor
EOS Evaporator outlet
temperature sensor
SGS Suction gas temperature
sensor
HPT
High pressure transducer Chilled
LPT
Low pressure transducer
Mode
Chilled
The same control is executed by using DSS (optional).
In case of DSS malfunction, [RS–2.0˚C] is used for control.
When DSS and RS are faulty, the unit should be stopped.
PF
No influence (continuous operation)
Frozen
Defrost
Chilled
No influence (continuous operation)
Defrost
PF
The same control is executed by using DRS (optional).
In case of DRS malfunction, [SS+2.0˚C] is used for control.
When DRS and SS are faulty, the unit should be stopped.
DEFROST-
The same control is executed by using DRS (optional).
ING
Chilled
Continuous operation
PF
Continuous operation
Frozen
Defrosting
Chilled, PF Continuous operation
Frozen
See the next page
Defrosting No influence (continuous operation)
Chilled, PF Continuous operation
Frozen
See the next page
Defrosting Defrosting start-up:Always permissible
Defrosting termination:The 90 minute timer count-up or
when EIS>90˚C or RS>set point
Chilled, PF Continuous operation
Frozen
See the next page
Defrosting No influence (continuous operation)
Continuous operation
PF, Frozen
Defrosting Refrigerant charge:No influence
Refrigerant release:LPT is used for releasing.
Chilled
Continuous operation
PF, Frozen
Defrosting Refrigerant charge:HPT is used for charging
Pump down:Pump down operation is not conducted
3-34
PF : Partial Frozen
Back-up content