Troubleshooting For Automatic Pti (J-Code) - Daikin LXE10E-A Service Manual

Marine type container refrigeration unit
Table of Contents

Advertisement

https://daikin-p.ru

6.3 Troubleshooting for automatic PTI (J-code)

Step
Content
P00
Basic data record
P02
Alarm check on all
sensor
P04
Power supply
check
P05
Compressor start
running check
P06
HPS check
P08
Pump down check
P10
Solenoid valve
check
P12
RS, SS accuracy
check
P14
HPT, LPT
accuracy check
P16
Evaporator fan
Hi/Lo speed
operation check
P20
Check on economizer
solenoid valve (ESV)
Alarm
Conclusion
code
No
No judgment
indication
Same as
Same as normal
normal
operation
operation
No
Same as normal
indication
operation
J051
Same as normal
operation
J061
Abnormal OFF point (1) HPS malfunction
J062
Not return
J064
High pressure does not rise.
J065
High pressure does not drop.
J081
Pump down
requires too long
time.
J101
Excessive
leakage of
solenoid valve
J121
Excessively large
temperature
difference between
RS and DRS
Excessively large
temperature
difference between
SS and DSS
J141
Excessively large
pressure
difference
between HPT
and LPT
J161
Abnormal operation
of evaporator fan
speed
J201
ESV does not
open.
Possible cause
Same as normal operation
Same as normal operation
Same as normal operation
(2) High pressure transducer
(HPT) malfunction
(3) Gas leak from Gauge
manifold
(No unit malfunction)
Blocked with contamination of
liquid solenoid valve
Leakage of hot gas by-pass
solenoid valve
Leakage of defrosting solenoid
valve
Leakage of discharge gas by-
pass solenoid valve
Liquid solenoid valve malfunction Check Liquid solenoid valve
Suction modulating valve malfunction Check Suction modulating valve
Injection valve malfunction
SS malfunction
RS malfunction
HPT malfunction
LPT malfunction
Evaporator fan and motor malfunction.
Magnetic contactor (EFH/L) and wiring
malfunction.
ESV coil malfunction
ESV malfunction
6-17
Check method
Same as normal
operation
Same as normal
operation
Same as normal
operation
(1) Check HPS
(2) Compare to Gauge
manifold
(3) Remove Gauge
manifold.
Try again S-PTI
Touch the outlet pipe of
the solenoid valve.
Touch the outlet pipe of
the solenoid valve.
Touch the outlet pipe of
the solenoid valve.
Check Injection valve
Compare the SS with
the DSS on the
controller panel.
Compare the RS with
the DS on the controller
panel.
Compare the high pressure
valve with the gauge manifold of
HPT (on the controller panel).
Compare the low pressure
valve with the gauge manifold
of LPT (on the controller panel)
Check Evaporator fan and motor.
Check magnetic contactor
(EFH/L) and wiring.
Check on ESV coil, wiring
and terminals.
Check on capillary tube
temperature on ESV outlet.