Connect cables
5. In case of LXE10E-1 : Check if auxiliary cable connection label
Cable connection label
sticked on the body
U
W
V
Yellow Gray
Red White Black
132 131 22 23
6. Connect the cables to the terminals.
Note 2. Don't drop the precharged refrigerant oil out after removing the blind flanges.
Charge
7. Open the discharge and suction side stop valves.
8. Vacuum and dehyadrate from service port r and t.
refrigerant
9. Then charge the refrigerant from service port t and e.
10. Check gas leakage especially at sunction/discharge
11. Fix the auxiliary insulation tape and fix the auxiliary packing tape
12. Seal with silicon sealant around
CAUTION
The preparation of refrigerant oil is not
required.
The compressor has been charge with
the oil.
for "LXE10E-1" is stuck on the cable
connection label of the compressor body.
Stick on
24
Attention !
Pay the attention to the cable connection.
Incorrect wiring may run the compressor
in wrong direction and may cause burn out.
(Refer to the clause 4.1.4 Refrigerant Recovery and charge)
flanges and flare nuts for injection piping/gauge piping.
using clamp band to the sunction
flanges.
the flare nut for gauge piping.
11. Fix the auxiliary
insulation tape
Auxiliary cable
connection label
W
U
V
Pink Gray
Brown Blue Black
132 131 22 23 24
Orange
(For LXE10E-1)
The unit does not have suction stop
valve. Be sure to adhere packing tape at
suction piping section to prevent
moisture from entering.
4-10
or
CE
12. Seal with
Silicon
Sealant
CAUTION