Daikin LXE10E-A Service Manual page 149

Marine type container refrigeration unit
Table of Contents

Advertisement

https://daikin-p.ru
Symptom
The low
pressure is
excessively low
The low
Solenoid valve
pressure is
internal leak(BSV,
excessively
DSV, HSV)
high
Solenoid valve
internal leak(ISV)
Faulty compression
by compressor
Cause
Continue from previous page
Remove the electronic expansion
valve coil
Blow air into the electronic expansion
valve and heat the valve by a dryer
Is pull-down possible?
Replace the valve
Replace the dryer
Lock-tight
(2) Metal touch
(1) Threads
Normal operation
Is HSV, DSV, BSV
outlet pipe hot?
Is the ISV
outlet pipe hot?
Circuit breaker OFF→ON
Is pull-down possible?
Replace the compressor
6-7
Checkpoint
NO
YES
Restore the electronic expansion valve
(see the pictures below)
(1) Apply Lock-tight sealant to the threads
(2) Apply Lock-tight sealant to the metal touch section
(3) Apply silicone sealant to the flare nut
(4) Fix the cable at two positions
(4) Tie wrap
YES (Hot)
*HSV: Hot gas solenoid valve
DSV: Defrost solenoid valve
BSV: Discharge gas bypass solenoid valve
NO (Cold)
YES (Hot)
*ISV: Injection solenoid valve
NO (Cold)
YES
NO
Remedy
Blow air onto here
Heat here by
a hair dryer
(3) Silicone sealant
Leak from solenoid valve
⇒Replace
Leak from solenoid valve
⇒Replace
Finish