Do you have a question about the LXE10E-A and is the answer not in the manual?
Questions and answers
Yang Ming-Ted Huang 黃泰穎
February 12, 2025
Hi , "Please inform me where in the official Daikin information I can find the following description, especially regarding the overhaul recommendations. Thank you. "For Daikin LXE10E-A series reefer units, it is generally recommended to perform a major overhaul every 40,000 running hours. Additionally, a minor overhaul should be conducted every 20,000 running hours. These intervals help ensure optimal performance and prevent unexpected breakdowns."
2 comments:
Mr. Anderson
February 12, 2025
Refer to the *Daikin Container Refrigeration Unit Service Manual* for the LXE10E-A series. This manual provides necessary information on operation, functions, and maintenance, including overhaul recommendations.
This answer is automatically generated
Yang Ming-Ted Huang 黃泰穎
February 19, 2025
Hi Anderson, because I can't find the overhaul recommendations in Service Manual* for the LXE10E-A series., please kindly advise where the overhaul recommendations from the content 1 to content 8 in Service Manual* for the LXE10E-A series. Thanks for your assistance.
Page 1
Marine type Container Refrigeration Unit Service Manual DAIKIN CONTAINER LXE10E-A TR 01-09B...
Page 2
Please read the contents of this manual prior to operation of the unit. This booklet will provide you with the minimum necessary information required to operate the Daikin refrigerated unit LXE10E-A. It covers all of the unit's functions from basics such as the names for each mode of operation, how to turn on the power supply, or change a setting temperature, to describing functions of product and maintenance service.
(for spare controller of DECOSⅢd, 2.3 Set point of functional parts and protection DECOSⅢc & DECOSⅢb) ....3-46 devices............2-12 3.8.4 LXE10E-1 & LXE10E-A Initial setting table 2.4 Operating pressure and running current ..2-13 into spare controller DECOSⅢd ..3-47 2.5 Operation modes and control......2-17 3.8.5 LXE10E-A Initial setting table into spare...
SAFETY PRECAUTIONS Always observe the following points before operating or inspecting a unit. DANGER Always turn off the main power supply to the facility before disconnecting the power plug. Always turn off the main power supply to the facility before inspecting the interior of the control box.
WARNING Do not touch the condenser fan while power to the unit is ON. Before removing the condenser fan cover, turn off the circuit breaker and disconnect the power plug. During air-cooled operation : Condenser fan may start and stop automatically for the refrigerant high pressure control.
CAUTION Before starting the unit, run the generator. Securely close the control box cover. Otherwise, it will allow water entry. Temperature Recorder (OPTION) Temperature recorder box cover Control box cover Quick-lock lever...
Page 8
CAUTION Wash the refrigeration unit with fresh water at PTI. Carefully flush the air-cooled condenser with fresh water to remove the salt that sticks to it.
Page 9
If any other refrigerant not specified is charged, it may cause problems with the unit. Use only Daikin specified oil (IDEMITSU, Daphne Hermetic Oil FVC46D) when replacing the refrigerant oil. If any other refrigerating machine oil not specified is charged, it may cause problems with the unit.
Page 10
CLASS 1 SPECIFIED PRODUCT BY THE HYDROFLUORIC REFRIGERANT RECOVERY LAW HFC IS USED FOR THIS PRODUCT AS A REFRIGERANT. (1) EMISSION OF HYDROFLUORIC SUBSTANCES INTO THE ATMOSPHERE WITHOUT PERMISSION IS PROHIBITED. (2) RECOVERY OF HYDROFLUORIC SUBSTANCES IS MANDATORY WHEN SCRAPPING THIS PRODUCT.
1. INTRODUCTION 1.1 Operation range Use the units within the following range. Item Operation range Ambient temperature range -30˚C to +50˚C (-22˚F to + 122˚F) Inside temperature range -30˚C to +30˚C (-22˚F to + 86˚F) 50Hz: 380V/400V/415V, 60Hz: 440V/460V Voltage Voltage fluctuation rate should be within ±10%...
1.3 Basic operation of refrigeration unit 1.3.1 Starting operation (1) Connect the power plug to the power supply. Insert the plug q suited to the power source voltage, and fasten the plug firmly. (2) Turn on the main power switch of the power source facility (outside the unit) (3) Turn on the circuit breaker w.
1.3.2 Checking during operation Checking items(precautions) Method of check 1. Check the compressor, fan, pipes, etc. for abnormal noise and vibration. Visual and auditory Visual check by using the moisture indicator 2. Check the refrigerant for shortage. Check the excessive charge.
1.3.4 Adjust the ventilation CAUTION Adjust the opening of the ventilation !0 according to the cargo. Keep the ventilation closed during transportation of the frozen cargo. When ventilation is not required set the handle When ventilation is required (chilled mode), to "CLOSE".
2. GENERAL DESCRIPTION 2.1 Main specifications Model LXE10E Item Condenser cooling system Air cooled type Controller DECOS3d Power supply AC 3-phase 380V/400V/415V 50Hz, 440V/460V 60Hz Compressor Hermetic scroll type (Motor output: 5.5kW) Evaporator Cross fin coil type Air-cooled condenser...
2.2 Names of components 2.2.1 Outside ●LXE10E Refer to the next page for detail of solenoid valves 2 2 2 1 2 0 1 7 1 6 Refer to page 2-4 for detail of compressor and refrigerant control devices...
Page 17
●LXE10E · Detail of solenoid valves · Models produced after Dec., 2004 ※RSV Dehumidification Control (option) · Models produced before Nov., 2004 ※RSV Dehumidification Control (option) ISV ESV [Valve] BSV :Discharge gas bypass Solenoid Valve DSV :Defrost Solenoid Valve...
Page 18
· Detail of compressor and refrigerant control devices DCHS Liquid Moisture Indicator Drier Receiver AMBS Sensor Valve DPR SMV LSV Service Port [Sensor] AMBS: Ambient temperature sensor DCHS: Discharge Gas Temperature Sensor DPR : Discharge Pressure Regulator Valve HPS : High Pressure Switch...
2.2.2 Inside ●LXE10E q Evaporator fan motor (EFM) w Evaporator e Supply air temperature sensor (SS) Data recorder supply air temperature sensor (DSS, optional) Recorder supply air temperature sensor (RSS, optional) r Evaporator outlet pipe temperature sensor (EOS) t Evaporator inlet pipe temperature sensor (EIS)
Page 20
· Inside Detail HuS (option) RS/DRS/RRS Evaporator Drain Pan Heater ※Re-Heater for Dehumidification Control (optional) [Sensor] DRS:Return Air Temperature Sensor for Datacorder (Optional) DSS:Supply Air Temperature Sensor for Datacorder (Optional) EIS :Evaporator Inlet Temperature Sensor EOS:Evaporator Outlet Temperature Sensor...
–4 –2 DAYS –6 –5 –4 –3 –2 –1 DECOS DAIKIN ELECTRONICCONTAINER OPERATION SYSTEM MANUAL UNIT DISPLAYSELECT M O D E DEFROST ON / OFF SELECT DOWN RNTER / ESC q Controller operation panel (EC3, 4) !2 Fuse (Fu1-6) w MANUAL DEFROST key...
Page 22
· Control box Inside detail ·Dry battery type MODEM CONTROLLER CC EFH EFL (optional) (DECOS 3d or 3c) Dip Switch for Emergency Operation (SMV adapter) PCC1 PCC2 PT/CT BOARD TrC (400V→24V,13V) BAT (9V) ·Rechageable battery type MODEM CC EFH EFL (optional)...
Page 23
· Control box Inside detail CN24 (Output from TB1) CN23 (Output from TB1) CN22 (Output from TB1) Fuse 1 CN26 (To Recorder) (SMV Adapter Board) EC6 or (To Rechargeable Battery Board) (To SMV) CN84 (To CPU Board) CN83 CN25 (Void)
Page 24
· Produced After May 2006(Connector Type) · Detail of Terminal Board and Short Circuit Connector Terminal Board Back of Controller Short circuit connector for emergency operation SCC1-2 (Red) SCC2 (Blue) SCC1-1 (Blue) Hus Sensor Board To Power of SMV...
Page 25
· Produced Before April, 2006(Screwed cramp type) · Detail of Terminal Board & Short Circuit Connector Terminal Board Back of Controller Short circuit connector for emergency operation SCC1-2 (Red) SCC2 (Blue) SCC1-1 (Blue) Terminal Board Reverse phase correction connector...
2.3 Set point of functional parts and protection devices Device name Actuation Set point Detection method Symbol High-pressure switch 2400kPa (24.47kg/cm High-pressure switch 1900kPa (19.37kg/cm Chilled mode –10.0°C to +30.0°C Set point temperature Mode selection (+14.0°F to +86.0°F) ※1 Frozen mode –30.0°C to –10.1°C...
2.5 Operation modes and control There are two main types of operation modes: the cargo cooling control mode and the unit inspection mode. The cargo cooling control mode is explained in this section. ※For the unit inspection mode, refer to section 3.9.
2.5.1 Frozen mode Control state transition and common control Thermostat ON (Pull-down range) ●Compressor Running ●Evaporator fan Low speed (L) RS > SP + 1.0˚C Continuous compressor running for ≤ ≤ 2 minutes or more and RS SP Thermostat OFF ●Compressor...
Page 33
(1) Set point temperature and control sensor When the set point temperature (referred to as SP hereafter) is –10.1˚C(+13.8˚F) or lower, the compressor is operated ON and OFF, in response to return air temperature. (2) Control qWhen the control temperature reaches SP (point A), the compressor and condenser fan are turned off.
2.5.2 Chilled and partial frozen mode Control state transition and common control START TS≧SP+1.5˚C TS<SP+1.5˚C Pull-down Heat-up TS≦SP+1.5˚C RS≧SP+1.0˚C TS≧SP+5.0˚C Capacity control (TS≦SP–3.0˚C TS≧SP+1.0˚C and 3-minutes elapse) and 3-minutes TS≦SP–0.5˚C or ( and 30-minutes elapse) elapse Overcool protection TS≦SP–0.5˚C...
Page 35
(1) Set point temperature and control sensor ™Chilled operation When the set point temperature is –10.0˚C (–140˚F) or higher,or –3.0˚C (+26.6˚F) or higher, the suction modulating valve (SMV) is controlled sensing the supply air temperature in order to adjust the cooling capacity.
2.5.3 Defrosting mode Start defrosting ●Defrost lamp (red) ON ●Pump down Defrosting range ●Compressor ●Evaporator fan ●Condenser fan ON/OFF ●Defrosting solenoid valve ON ●Hot gas solenoid valve ON Is terminating condition OK? Defrosting lamp (red) OFF Evaporator fan On after delay of 60 seconds...
Page 37
Defrosting operation (1) Defrosting system A hot-gas defrost system is adopted in the units; i.e. the high temperature and high pressure refrigerant (hot gas) from the compressor is sent to the evaporator and drain pan for defrosting. Since the evaporator is heated directly by the hot gas (refrigerant), defrosting can be performed effectively.
Page 38
(4) Defrosting termination Defrosting will be terminated when any one of the following three conditions is satisfied. qThe below figure is satisfied during defrost. Status before defrost Termination INRANGE EOS≧30.0˚C OUTRANGE EOS≧30.0˚C+RS/DRS≧15˚C w90 minutes have elapsed. eAny one of protective devices is activated.
2.5.4 Dehumidification (Optional) The unit have dehumidification control by a reheat coil, which is fitted under the evaporator coil. To execute dehumidification, controller setting is required. (Refer to Page 3-12) In dehumidification, the Reheat Solenoid Valve (RSV) opens to give high temperuture and high pressurized refrigerant to reheat coil.
2.5.5 Common control The following are controlled in different operation modes. (For the details, refer to the following pages.) Operation mode Control name Control content Partial Frozen Chilled Defrost frozen The compressor is operated on and off to A Compressor ON/OFF control ○...
Page 41
Common control A : Compressor ON/OFF control When the control temperature reaches the set temperature or lower, the compressor is stopped. When the control temperature rises and becomes higher than the [set point temperature +1.0˚C], the compressor runs again.
Page 42
• By condenser fan When the ambient temperature is low during the air-cooled operation, the condenser pressure (high pressure) will decrease. Accordingly, the low pressure will decrease. In order to prevent this situation, when the high pressure becomes set point or lower, the condenser fan stops to prevent the high pressure from excess dropping.
Page 43
I : Capacity control In the chilled mode operation, adjusting cooling capacity makes the supply air temperature stable at the set point temperature (SP). The capacity control is executed by adjusting the opening of suction modulating valve (SMV) between 3 to 100 %.
3. ELECTRONIC CONTROLLER 3.1 Function table ●DECOS 3c/d (Daikin Electronic Controller Operation System) (Note) [PC]: Functions using personal computer Function division Function DECOSⅢc/d ✓ Control function • Temperature control ✓ • Defrosting control • Humidity control Optional ✓ Initial setting •...
Page 45
Function division Function DECOSⅢc/d ✓ Self-diagnosis and • Open-phase running ✓ automatic back-up • Over current running ✓ • CPU and peripheral device (electronic controller) ✓ Manual inspection • Compressor running hour indication ✓ • Evaporator fan individual operation (high speed) ✓...
DAYS –6 –5 –4 –3 –2 –1 DECOS DAIKIN ELECTRONICCONTAINER OPERATION SYSTEM Note) As a substitute of "MODE key", G-SET "G-set key" available on some models as well. Sheet key q SUPPLY LED (Lights when "supply air temperature" is indicated.) u IN RANGE LED (Lights when the control temperature is in range.)
Page 47
Function of operation key ●UNIT ON/OFF key ●UP key UNIT ON/OFF To select the item to be set in To start or to stop the unit the selected mode. operation. The controller has a memory ●DOWN key DOWN function.
Page 48
DISPLAY q Indicate the temperature data required to be converted into "˚F" C ˚ on the LED or the LCD. F ˚ DISPLAY C ˚ w Press the key, then the temperature data displayed in "˚C" F ˚ is converted into "˚F" for one minute.
3.3 Operation procedure 3.3.1 Operation procedure flow chart ※3 Battery mode Power off No key operation for 30 sec. Circuit Breaker ON Circuit Breaker OFF after setting change Unit off ( OFF when no setting change) I/O ON I/O OFF All Lighting (for 3 sec.)
Page 50
Check on settings and operation conditions ※1. Current indication mode (indication of operation conditions) ●Supply air temperature (SS) Indicates the unit operation conditions. ●Return air temperature (RS) Page 3-9 ●Defrost interval ●Alarm ●Setting point humidity and humidity (OPTION) ※2. Operation setting mode ●Temperature settings...
Page 51
Indication of detailed data alarm and PTI ※6. Sensor indication mode ●Discharge gas temperature (DCHS) Each sensor value can be indicated. ●Suction gas temperature (SGS) ●Modulating valve opening ●Electronic expansion valve opening ●High pressure (HPT) ●Supply air temperature (SS) ●Low pressure (LPT)
3.3.2 Mode operation procedure 1. CURRENT (Operation state) INDICATION MODE Supply air temperature (SS), return air temperature (RS), defrosting interval, currently existing alarm, set point humidity, and humidity are indicated. Turn on the circuit breaker and the UNIT ON/OFF key after turning the...
2. OPERATION SETTING MODE Control temperature, defrosting interval, and control humidity (optional) can be set. To change to the OPERATION SETTING MODE, press the key while CURRENT (Operation the unit is in the CURRENT INDICATION MODE. state) INDICATION MODE...
3. BATTERY MODE When commercial power is not available, the following functions are available by using the built-in wake up battery. • Indication of inside supply air temperature (SS) and return air temperature (RS) • Setting for control temperature, control humidity and defrost interval...
4. MODE OPERATION G-SET MODE Press the key (or key) in current indication mode to go to MODE operation. All indication Lights on (for 3 sec.) Starting Preparation (for 18 sec.) ※ Current indication (Operation state) MODE MODE OPERATION In mode operation, the following settings/operations are available.
Page 56
Setting item LED panel LCD panel Setting method Current indication mode –– –– –– MODE OFF, 11, 12, 13, 14, 15 G-SET Select the energy unit: kVA saving set point by G-set operation using key, Note 1) and press the key to determine the setting.
5. LED display LIGHT-OFF MODE The controller LED display is turned off with this mode. ※ Activation of the panel (LED) lighting off mode. To activate the panel (LED) lighting off mode, set the LED lighting off function "dISP" in "11. Basic setting mode"...
6. SENSOR INDICATION MODE Each sensor value, the suction modulating valve (SMV) opening, and the electronic expansion valve (EV) opening can be checked. The following items are displayed: High pressure (HPT), low pressure (LPT), voltage (PT1), total current (CT1), compressor current (CT2),...
Page 59
6. SENSOR INDICATION MODE (continued) LED: The control temperature is displayed. CURRENT LCD: The compressor running current is displayed. SENSOR-2 (CT2) The display reads: " CT A". (In Ampere.) LED: The control temperature is displayed. AMBIENT TEMPERATURE LCD: The ambient temperature is displayed.
Page 60
6. SENSOR INDICATION MODE (continued) LED: The control temperature is displayed. PULP TEMPERATURE LCD: The pulp temperature is displayed. SENSOR 1 The display reads: " US C". (USDA 1) (optional) (In ˚C or ˚F.) LED: The control temperature is displayed.
7. TEMPERATURE RECORD SCROLL MODE The control sensor value record is shown in sequence (scroll) starting with the latest data. The latest control temperatures for a maximum of 7 days are displayed. <Mode selection procedure> All indication Lights on (for 3 sec.)
Page 62
Temperature record scroll function The control sensor value record for the last 7 days is displayed in sequence (scroll) beginning with the latest one and ending with oldest one, so that easy inspection of the previous operation data is enabled on board.
Page 63
● Example of TEMPERATURE RECORD SCROLL INDICATION MODE ※ It is assumed that the control temperature is the supply air temperature (SS) and the logging interval is 1 hour, and the current date and time are June 27, 2002, 14:00.
8. ALARM RECORD SCROLL MODE The alarm record is shown in sequence (scroll) starting with the latest data. The latest alarms for a maximum of 7 days are displayed. <Mode selection procedure> All indication Lights on (for 3 sec.)
Page 65
Alarm record scroll function The alarms detected over the last 7 days are displayed on the controller which scrolls through them at the rate of one sec/alarm. < Operation procedure > The LED indicates alarm codes, and the LCD displays date and time.
9. PTI RECORD SCROLL MODE The record is shown in sequence (scroll) starting with the latest data. <Mode selection procedure> All indication Lights on (for 3 sec.) Starting Preparation (for 18 sec.) ※ 1 Current indication ※ 9 PTI ※...
3.3.3 Setting flow chart This configuration setting flow shall be utilized, when CASE 1) USDA transportation setting is required (※10 Optional Function Setting) CASE 2) Container ID shall to be subjected to change from another container for emergency use.
10. OPTIONAL FUNCTION SETTING MODE <Key operation to enter/exit> Power OFF Circuit Breaker ON Circuit Breaker OFF after setting change Unit OFF OFF when no setting changed) I/O ON I/O OFF All indication lights on (for 3 sec.) for 3 sec.
11. BASIC FUNCTION SETTING MODE <Key operation to enter/exit> Power OFF Circuit Breaker ON Circuit Breaker OFF after setting change Unit OFF OFF when no setting changed) I/O ON I/O OFF All indication lights on (for 3 sec.) for 3 sec.
Page 71
To set the power input: Select "Sing" or "dUAL" on the LED when the LCD displays "OC-SET" . Whenever the key is pressed, the indication of "Sing" or "dUAL" is INPUT POWER changed. Press the key to determine the setting.
12. OPTIONAL CONDITION SETTING MODE Key operation to enter/exit < > Power OFF Circuit Breaker ON Circuit Breaker OFF after setting change Unit OFF OFF when no setting changed) I/O ON I/O OFF All indication lights on (for 3 sec.) for 3 sec.
Page 73
12. OPTIONAL CONDITION SETTING MODE (continued) H002 code is displayed when the integrated time of Out-of "In-Range" reaches 2 hours. Select "1"hour, "2"hours, "3"hours, "4"hours, "5"hours or "10"hours on the LED H002 when the LCD displays "H002". Whenever the key is pressed, the indication of the selection from "1"hour to "10"hours changes.
12. OPTIONAL CONDITION SETTING MODE (continued) "d2 – –" message displays the total time in hours, that the temperature was above set point +2°C. The code will be displayed after the selected time which can be set to: "1"hour, "2"hours, "3"hours, "4"hours, "5"hours, or "10"hours.
<Key operation in this mode> Whenever the key is pressed, the indication changes. Turn OFF the power breaker to confirm the setting. To input the container I.D. (No.): CONTAINER I.D. Press the key when the LCD displays "SET I.d", then display "i.d.- (No.) INPUT...
3.4 Alarm display and back-up function 3.4.1 Alarm list Alarm Alarm Alarm content Action with alarm grouping code F101 HPS activated within 2 seconds after operation start or protection device Unit stops activated 5 times at start-up operation or Fuse 1 brown (Refer to Page 7-7).
3.4.2 Back-up operation at sensor malfunction PF : Partial Frozen Sensor malfunction Mode Back-up content Supply air temperature Chilled The same control is executed by using DSS (optional). sensor In case of DSS malfunction, [RS–2.0˚C] is used for control.
Page 78
●Back-up for temperature sensors (EIS, EOS, SGS) at frozen mode (superheat control) Evaporator inlet sensor Evaporator outlet sensor Compressor suction gas sensor Back-up operation Normal Normal Normal superheat control Normal Normal Abnormal superheat control Liquid refrigerant back prevention Normal...
DECOS 3c/d controller can use two types of batteries; DRY or Rechargeable (Optional). The battery is installed to the lid of the controller. DRY Battery: 9V block battery. (This can be purchased locally.) Rechargeable: DAIKIN original rechargeable battery 3.5.2 Function This battery is used without main power supply for the following functions.
2) Battery check Battery check button Rechargeable Battery Red Green To test residual voltage, check color of LED by pressing battery check button. Green : Full charge : Check again after charging for 8 hrs, then --- Green : Full charge...
3.6 Information interchange with personal computer The electronic controller DECOS 3c/d has a internal memory function to record the set point temperature, inside temperature, operation mode, occurrence alarm and the report of automatic PTI during transportation in addition to the normal operation control.
3.6.1 Data logging The data logging function is to store operation data which is generated during navigation. There are seven kinds of logging data. As to Tripdata, its logging interval can select from 15, 30, 60 (default) and 120 minutes.
3.6.2 Software configuration MAIN MENU SUB MENU Explanation of functions Remarks LOGGER DATA TRIP DATA Data recorded in the logger is read No information DOWNLOAD USDA DATA from the controller onto the personal appears on the 4-PULP SENSORS DATA computer (disk or hard disk).
Page 84
MAIN MENU SUB MENU Explanation of functions Remarks MAKE REPORT TRIP REPORT Reports are made based on record USDA REPORT data read from the logger. 4-PULP SENSOR REPORT PTI REPORT ALARM REPORT MONITOR REPORT EVENT REPORT MAKE SET CONTAINER I.D.
3.7 Inspection procedure for the electronic controller DECOS 3c enables the internal data of the controller CPU (RAM data) to be displayed on the monitor of a personal computer by connecting the two with a communication cable. This makes it possible to preform an easy inspection of the controller and diagnose any defect.
3.8 Controller replacement and the initial setting 3.8.1 Controller replacement <Replacement procedure for the controller> (1) Remove speed bolts (2 pcs) on the controller body, then remove the connector. Be sure to keep voltage indicator, the battery and the battery fixing plate for reinstallation.
Applicable model LXE10E-A, LXE10E-1, LXE10D 1. Compatibility, Controller DECOSⅢd to Ⅲc & Ⅲb ※1 Controller DECOSⅢd is standard for all LXE10E-1 and ※6 LXE10E-A manufactured from July 2005 ※2 Controller DECOSⅢc is standard for ※7 LXE10E-A manufactured prior to July 2005 ※3 Controller DECOSⅢb is applied for LXE10D.
Download the latest software from DAIKIN HOME PAGE as follows. The unit can be operated with factory installed software loaded in the spare controller. However Daikin requests to up-grade the software to the latest version for the best operation. 'http//www.daikin.com/service...
3.9 PTI (Pre-Trip Inspection) AND PERIODIC INSPECTION The controller (DECOS 3c) has the automatic PTI function, which consists of three process of SHORT PTI (referred to as S.PTI hereafter), FULL PTI (referred to as F.PTI hereafter) and MANUAL CHECK (referred to as M.CHECK hereafter)
3.9.1 Inspection item The periodic inspection and adjustment of components (if required) is recommended to ensure continued successful operation. The following table shows an example of the inspection plan. Inspection item Inspection content year 4 year 8 year Inspection for physical damage...
Page 95
Inspection item Inspection content year 4 year 8 year Dryer replacement Function inspection and replacement of liquid moisture indicator Conditions of fasteners on the refrigerant pipes and gauge pipes Condition of thermal insulation of refrigerant pipe Evaporator coil cleaning...
Page 96
Inspection item Inspection content year year year 1) Sensor error inspection 2) Chart drive inspection Temperature recorder 3) Recording operation inspection inspection 4) Loose terminal 5) Chart drive dry battery inspection 6) Check of pen lifting battery 1) Check of wake-up battery...
3.9.2 Automatic PTI (Pre-Trip Inspection) ● The automatic PTI function is provided so as to ensure correct inspection and to shorten inspection time. (Refer to section 3.2 for operation of controller) (1) Appearance inspection of unit Physical damage Casing insulation through hole area...
3.9.2.1 PTI selection mode The test mode of FULL (F.PTI), SHORT PTI (S.PTI), and MANUAL CHECK (M.CHECK) can be selected. <Mode selection procedure> Power OFF Circuit Breaker ON Unit OFF I/O ON I/O OFF All indication Lights on (for 3 sec.) for 3 sec.
● Automatic PTI enable conditions Water cooled Air cooled Ambient temperature condition operation operation –10˚C < Ambient temperature ≦ 43˚C ✕ S. PTI When the ambient temperature is above 43˚C or below –10˚C, the correct judgment may not be possible.
3.9.2.3 Full PTI (F.PTI) F.PTI consists of S.PTI and operation tests. ●Step display and contents (step P00 to P32 are as same as S.PTI) Step Content ●F.PTI flow chart Check on pull-down to 0˚C Check on controllability of chilled UNIT ON/OFF key: on mode operation.
3.9.2.4 Alarm list during PTI (Pre-Trip Inspection) The alarm during automatic PTI are concerned with PTI inspection items in addition to those during normal operation. The alarms at automatic PTI are indicated in J ※※※., being separated from those during normal operation.
3.9.2.5 Manual check (M.CHECK) Since the components are operated individually differing from S.PTI and F.PTI, the steps can be respectively selected and executed. However, any error occuring during execution of M.CHECK will not be included. Turn the UNIT ON/OFF key off to terminate the M.CHECK.
Page 103
MANUAL CHECK SELECTION MODE The LED displays the values of following items: Compressor operating time, Evaporator fan motor high-speed running current, Evaporator fan motor low-speed running current, Condenser fan motor running current, Battery life, Horse power, Elapsed time after trip start, Evaporator fan motor running time, Condenser fan motor running time, and Controller software version.
3.10 Chartless function The controller provides the temperature recorder function. In the case of recorder-equipped units, checking for the temperature on the chart recorder will provide ease of monitoring the state of tripping. Since recent controllers are available for long and accurate temperature recording, non-recorder- equipped units have been increasingly used.
Page 105
●Displaying temperature change trend: The temperature change trend is shown in the leftmost LCD. However, this display is shown only when all segments are in the same temperature range. Trend indication Condition Temperature rise trend The latest the oldest –...
3.10.2 P code (Pull down time indication) The control temperature and pull-down time are indicated alternately during pull-down operation. When the pull-down is completed, the P code will be deleted. P001: Lasts the pull-down for 1 hour. /P002: 2 houes passed since pull-down started.
3.10.3 Chartless code display function The chartless code represents the coded inside air temperature. Select "ON" of the chartless code setting to indicate the code on the LED. For the chartless code setting, refer to the "OPTIONAL CONDITION SETTING MODE" on the page 3-29〜3-31.
3.10.3.2 H-code H001 =The alarm is displayed when the control temperature does not decrease by 3˚C or more every 4 hours during pull-down operation. Inside If "t" is smaller than 3˚C, code "H001" appears. Temperature ※ This criteria (3˚C) can be adjusted from 1, 2, 5 or 10˚C.
Page 109
H005 =The alarm is displayed when the control air temperature is out of "in-range" and defrosting was performed three times while the control air temperature does not return to in-range. SP+1 30min Figure5 Out range timer H006 =Alarm is displayed when the temperature difference between the control sensor and record sensor is 2˚C for 1 hour, or more.
3.10.3.3 d-code: The d-code shows the current operation state of the unit. Example d101: • This code "d101" will be displayed when the total time above set point +1˚C reaches 1 hour. The code "d102" will then be displayed when the total time above set point +1˚C reaches 2 hours.
¡Manual defrosting initiation ¡Header information changing (*1) According to the relationship among slave modem, Master modem and controller, items which can monitor and/or command are different. Please contact DAIKIN sales office if you have a specific item to monitor/command. 3-68...
4. SERVICE AND MAINTENANCE CAUTION 1. Use the pressure indicating function 4.1 Maintenance service of the controller to check the working 4.1.1 Collection of refrigerant pressure as much as possible qWhen release the refrigerant from the instead of using the gauge manifold...
Page 113
(2) Removal of gauge manifold ●Location of service ports on high pressure Turn the valve handle of coupler and low pressure sides counterclockwise (the push pin is pulled Service ports on high pressure and low up). Slide the sleeve upward while fixing the...
4.1.3 Automatic pump down An automatic pump down system is applied to the unit to prevent the unit from extra decrease of low pressure due to pump down operation or burning of scroll compressor due to a close stop valve.
Page 115
(2) Automatic pump down operation Once the automatic pump down is started, all of the service works from refrigerant collection into the receiver, to the equalizing in suction piping system, can be executed automatically. When "Good" is displayed, service works such as replacing the dryer, etc. can be conducted without any other operation.
4.1.4 Refrigerant Recovery and Charge Evaporator service port Condenser Check valve Drier Receiver Compressor service port Service work Service port Remarks High pressure Pressure Check Low pressure Recover refrigerant from port t after operating [1] Refrigerant Automatic Pump-Down first.
Page 117
(1) Operation Pressure Check (3) Refrigerant Recovery Check high pressure from the service port w qOperate Automatic Pump Dpwn. wRecover refrigerant from port t. on the compressor discharge. Check low pressure from the service port q on the compressor suction.
Page 118
(a) Vacuum dehydrating 2.Replace the manifold gauge hose to port e and add the liquid refrigerant. After recovering, connect the vacuum pump to the service ports r and t at the Then if it reached to the specified liquid receiver outlet piping and discharge...
4.2 Main components and Flare nut for injection piping maintenance Discharge flange Flare nut for gauge 4.2.1 Scroll compressor piping The compressor is of a hermetic scroll type Suction flange Terminal box with the built-in motor so that there are less places where refrigerant may leak.
Page 120
(2) Removal of compressor 1. Recover the refrigerant from service port r on discharge line Recover and t at receiver/water cooled condenser outlet. refrigerant (Refer to the clause 4.1.4 Refrigerant Recovery and charge) 2. Close the discharge and suction side stop valves on the compressor.
Page 121
Connect cables 5. In case of LXE10E-1 : Check if auxiliary cable connection label for "LXE10E-1" is stuck on the cable connection label of the compressor body. Cable connection label Auxiliary cable sticked on the body connection label Stick on...
Page 122
5. If the oil level can be seen on the oil level (3) Removal of excess refrigerant oil after gauge, conduct the step 4 oil return compressor replacement The oil plug, oil level gauge and "Removing oil operation again.
● How to use bearing drawing tool on the market. 4.2.2 Fan and fan motor (1) Specification Bearing drawing tool Evaporator Condenser Model Propeller fan Size 440mm 300mm Model 3-phase squirrel-cage Boss induction motor When the shaft of the bearing...
4.2.3 PT and CT board (EC9756) r PTI (R-S voltage) Two function of the measuring device and t Connector (CN2) for main circuit protector are integrated on this printed-circuit board. This board works as an interface between the main circuit (high voltage) and the controller.
Page 125
(2-3) Removal of mounting plate Check the following table to see if the mounting plate should be removed. If the mounting plate must be removed, remove the four screws and dismount the mounting plate. Over current setting and removal of mounting plate...
4.2.4 Electronic expansion valve (2) Replacing the body q Loosen the lock nut, then remove the coil. ● Model Coil : EBM-MD12DM-1 (Put two wrenches onto the locknut and the Body : EDM-B804DM-1 unit to remove the coil.) This unit adopts an electronic expansion valve.
4.2.5 Suction modulation valve q Upper rubber e Binding band cover The flow rate of suction gas is controlled w Lower rubber between 10 to 328pls (3 to 100%) by a stepping cover ass'y motor in order to conduct capacity control operation.
2. Replacement of body 4.2.6 Drier (1) Remove the coil. Refer to the section 1. The drier automatically absorbs moisture in "Replacing the coil" for removing procedure. the refrigerant while it is circulated. It also (2) Remove the heat insulator q for the SMV after commonly works as a filter to remove dust in cut the binding band w.
4.2.7 Solenoid valve (1) Replacing the coil q Remove the lead wire connector from the inside Two kinds of solenoid valves are employed for of the control box, and cut and recover the binding the unit. band which fastens the lead wire.
4.2.8 Discharge pressure regulating valve 4.2.9 Check valve ● Model KVR15 ● Model LCV(B)5 (1) Replacing the valve (1) Replacement procedure q Remove the protection cap to conduct brazing q Remove the pipe clamp which fixes the for the valve body.
4.2.10 High-pressure switch (HPS) 4.2.11 Low pressure transducer (LPT) ● Model ACB-KB15 Produced before Produced after ● Set point OFF : 2400kPa (24.47kg/cm Model September,2004 October,2004 : 1900kPa (19.37kg/cm Transducer type SPCL02 NSK-BC010F When the refrigeration pressure of the unit...
4.2.13 Air-cooled condenser and evaporator y Apply the heat shrinkage tube in the following position, then shrink it with hot air of a dryer. This finned coil is compact and has uniform heat exchanging performance and high heat w Connector...
ATTENTION 3 !! In the case of overcharge or shortage of refrigerant, recover all refrigerant from the unit and charge with new refrigerant R134a with rated charged amount of 4.6 Kg (LXE10E-A) or 5.4 Kg (LXE10E-1). Refrigerant overcharge may cause scroll compressor damage.
4.2.16 Evacuation and dehydrating Boiling point of water (˚C) Atmospheric pressure(mmHg) Vacuum degree(mmHg) After repairing the refrigerant system, vacuum- –705 dehydrate the system before charging the –724 refrigerant. 26.7 –735 24.4 –737 Vacuum-dehydrating is the process to make the 22.2...
Page 135
Vacuum holding test qVacuum-dehydrating (first time) Hold the system at a pressure of ..2 hours wVacuum-breaking (first time) –755mmHg or lower for 1 hour or longer, and confirm that the vacuum reading does Nitrogen gas is pressurized to 0.5kg/cm not rise on the vacuum gauge.
5. OPTIONAL DEVICES (1) Specifications ● Model DER9601A The following optional devices are available for ● Power supply AC13V 50/60Hz some models. As for other options, see Chapter 8 ● Recording temperature range –30.0 to +25.0 °C in the SUPPLEMENTARY MANUAL.
Page 137
(2) Devices and schematic wiring diagram 2) Calibration function 1) Devices Calibration switch INC : To increase Device Location INC. temperature figure Temperature recorder board In the temperature recorder box OFF. ADJ. DEC : To decrease Recorder return air sensor (RRS) Evaporator suction area DEC.
5.1.2 Rechargeable battery type ●Temperature record with power supply turned off When the power supply is turned off, the pen will move to the outer circumference of recording sheet simultaneously. Power supply is turned off. ●Rechargeable battery The rechargeable battery is equipped on the electronic temperature recorder.
Type of USDA sensor should be set. 5.2.3 USDA sensor calibration USDA requires sensor calibration every transportation and report each offset figure. Free-supply downloading software enable to assist this. Please refer to "Operation manual for Daikin Container Communication Software". 5.2.4 USDA transportation requirement Cargo and refrigeration unit shall be required pre-cooling before cargo loading.
Page 140
●An example of installation of USDA receptacle inside USDA sensor receptacle Cargo thermo sensor receptacle PC port receptacle ●USDA sensor Connect to receptacle...
5.3 TransFRESH Attachment for the TransFRESH CA devices are provided to control the internal atmosphere (quantity of O and CO Use the CA devices according to the Operation Manual supplied by TransFRESH. The controller and sensor included in the CA devices are installed by the TransFRESH's agents before each transportation.
Page 142
●An example of installation of CA devices, inside q TransFRESH ASS'Y A4&A5 CABLES W/MOUNTING BOX...
6. TROUBLESHOOTING 6.1 Refrigeration system and electrical system If the unit does not work properly, refer to the following table to find causes of trouble and provide appropriate measures. Symptom Cause Checkpoint Remedy A. Neither Faulty power supply Voltage on primary side of circuit...
Page 144
Symptom Cause Checkpoint Remedy F. Evaporator Faulty power supply of fan and compressor system Is the magnetic condenser Burnt-out of compressor Check for disconnection of contactor for compressor compressor motor coil fan run, but motor (disconnection) turned ON? Check the terminals...
Page 145
Symptom Cause Checkpoint Remedy Disconnection of compressor fuse Fu1 circuit Is the fuse Fu1 circuit does not Replace the fuse Fu1 disconnected? operate Faulty controller Faulty PT/CT board Replace the controller or PT/CT board Power supply R or T-phase is...
Page 146
Symptom Cause Checkpoint Remedy Indicator flashes Refrigerant when the RS is shortage Gas leak check Gas leaks⇒Restore the gas leaking portion -10˚C or less Blocked pipe (parts) during frozen (including solenoid operation valves) Trap of air in refrigerant system...
Page 147
Symptom Cause Checkpoint Remedy The high Check for leak from pressure is Solenoid valve solenoid valve during pull-down. Is the Leak from solenoid valve excessively internal leak temperature in the piping on the BSV, HSV, ⇒Replace the solenoid valve...
Page 148
Symptom Cause Checkpoint Remedy Reset opening of EV, SMV The low Faulty opening of (Circuit breaker ON) pressure is electronic excessively low expansion valve (EV) Is pull-down possible? Faulty opening of Normal suction modulsting valve (SMV) Low air volume...
Page 149
Symptom Cause Checkpoint Remedy Continue from previous page The low pressure is Remove the electronic expansion excessively low valve coil Blow air onto here ↓ Blow air into the electronic expansion Heat here by a hair dryer valve and heat the valve by a dryer...
Page 150
Symptom Cause Checkpoint Remedy Heating operation The high pressure is excessively low Faulty operation of The discharge valve gas temperature Is the outlet piping of HSV, Faulty operation of HSV, (HSV or DSV) DSV cold? DSV⇒Replace is low The low...
Page 151
Symptom Cause Checkpoint Remedy Operating temperature The control is hunting temperature is unstable Is the difference in Faulty low pressure pressure between the transducer LPT Replace the LPT pressure gauge and LPT 30 kPa or more? Faulty discharge pipe...
Page 152
Symptom Cause Checkpoint Remedy Temperature continues Temperature to decrease continues to decrease Check for disconnection ・Disconnection of Replace the Fu2 in the Fu2 circuit fuse (Fu2) circuit Is the DSV outlet ・Faulty operation Check operation of the DSV pipe cold? ⇒Replace the DSV...
Page 153
Symptom Cause Checkpoint Remedy Abnormal ※ As for the manual defrost, refer to P.2-23. Manual defrost frosting on compressor ・Frosting on terminal cover ・Frosting on Defrost completed compressor head Dusts caught in Is the ISV injection solenoid outlet pipe frosted?
Page 154
Symptom Cause Checkpoint Remedy The condenser fan continues rotating The air cooling Water pressure evaporator fan switch WPS will continues not operate ・Water pressure is low rotating ・Water temperature is The high pressure is Check the water pressure, excessively high...
6.2 Alarm codes on electronic controller If any alarm occurs, search its cause and repair it referring to the following table. Be sure to check the connectors in the electronic controller as the poor contact of them may cause the controller alarm codes.
Page 156
Alarm code Content Possible cause/checkpoint Operating current of the compressor is great Single phase operation due to faulty contact E103 ・Magnetic contactor for compressor (Electronic type OC) ・Compressor cable ・Compressor terminal Malfunctioned equipment ・Compressor lock ・Actuation of thermal protector CTP for compressor ・Faulty PT/CT board (EC5)
Page 157
Alarm Content Possible cause/checkpoint E303 Humidity setting request System malfunctioned E305 Defrost timer setting request ・Faulty controller E307 Calendar setting request Faulty operation E311 Trip start setting request ・Wrong initial setting of controller E401 Supply air temperature sensor (SS) fault...
Page 158
Malfunction and Alarm LXE10E when the is disconnected or loosened. connector Malfunction or Alarm Applicable to Location Socket No. when the connector is disconnected or loosened. LXE10D CN81 No Alarm······No power supply to Controller ----- (White) CN82 (Red) No Alarm······No power supply to Controller...
6.3 Troubleshooting for automatic PTI (J-code) Alarm Step Content Conclusion Possible cause Check method code Basic data record No judgment indication Alarm check on all Same as Same as normal Same as normal operation Same as normal sensor normal...
Page 160
Alarm Step Content Conclusion Possible cause Check method code Check on J221 BSV does not BSV coil malfunction Check on BSV coil, wiring discharge gas by- open. and terminals. pass solenoid BSV malfunction Check on outlet piping valve (BSV)
6.4 Diagnosis based on the recording chart Set temperature 0˚C Occurrence read out from the recording chart Defrosting is periodically executed by the timer Abnormal content and abnormal point Normal Set temperature 0˚C Occurrence read out from the recording chart...
Page 162
Set temperature 0˚C Occurrence read out from the recording chart Though the temperature record is normal, the temperature rapidly rises. Abnormal content and abnormal point The compressor stops due to malfunction or the fusible safety plug is molten. Set point temperature –...
Page 163
Set point temperature 0˚C Occurrence read out from the recording chart When defrosting, the inside temperature temporarily drops. Abnormal content and abnormal point Since the liquid solenoid valve is not closed, pump-down operation before defrost starts is not performed, and cooling operation continues with the evaporator fan stopped.
6.5 Emergency operation 6.5.1 Emergency operation of controller In case of the controller malfunction, emergency operation can be executed by using emergency operation kit. (1) Components to be prepared (emergency operation kit) Short circuit connector --- Stored on the back of CPU/IO board case in the control box.
6.5.2 Short circuit operation of controller ●Models produced after May,2006 (Connector type terminal board) Cooling Operation Heating Operation Disconnect CN82 (White) q Turn the circuit breaker OFF. For cutting off SMV adapter w Disconnect the power supply the power to...
Page 166
●Models produced before April,2006 (Screwed cramp type terminal board) Cooling Operation Heating Operation Disconnect CN82 (White) q Turn the circuit breaker OFF. For cutting off SMV adapter w Disconnect the power supply the power to connector CN82(White) on SMV CPU board adapter board.
6.5.3 Opening adjustment of electronic expansion valve In case of the controller malfunction or faulty electronic expansion valve coil, electronic expansion valve can be operated with fixed valve opening by using emergency cap. Caution If the electronic expansion valve is energized while the coil is removed from valve body, the coil driver with which the valve needle is pushed protrude excessively.
6.5.4 Opening adjustment of suction modulation valve: In case of emergency, there are two ways to open the suction modulating valve manually. It is important to follow these steps in this sequence. Use step 1 first. If this is not working, then use step 2.
6.5.5 Automatic Back up for supply / return air temperature sensors When the unit is equipped with the data recorder sensors, the following emergency operations are available. When the DRS and DSS are used for the emergency operation, DATA RECORDER SENSOR ON/OFF SETTING to be set OFF.
7. APPENDIX 7.1 Standard tightening torques for bolts Tightening torque Bolt size Main part kgf cm lbf ft Small parts Solenoid valve 12.2 Access panel Evaporator fan motor Condenser fan motor 12.3 Control box Service door Evaporator fan motor mounting base Compressor suction flange 25.2...
7.11 Electric wiring pilot lamps and monitoring circuit Four pilot lamps which indicate operating mode are mounted on the controller in the control box. Pilot lamp Color Operating condition COMP. Green The compressor is running DEFROST The unit is under defrosting operation...
7.14 Stereoscopic wiring diagram (Connector type terminal board and rechargeable battery) Line color B L K: Bl a ck, BL U: Bl u e , GRY : Gr ey (6) At the two tightening positions of round crimp terminals...
7.16 Stereoscopic wiring diagram (Connector type terminal board, temperature recorder and dry battery) Line color B L K: Bl a ck, BL U: Bl u e , GRY : Gr ey (6) At the two tightening positions of round crimp terminals...
7.18 Stereoscopic wiring diagram (Screwed cramp type terminal board, temperature recorder and dry battery) T B 1 RCD(YORK) T e s 6 2 ※ 5 ※ E C 1 C N 1 6 6 ※ T r c 1 ※...
8. OPTIONAL FUNCTIONS MANUAL Some models may be equipped with the options shown below. Applicable options are marked with ○-marks. 8.1 Electronic temperature recorder 8.2 Electronic controller 8.1.1 8.1.2 8.2.1 8.2.2 8.2.3 8.2.4 8.2.5 8.2.6 8.2.7 8.2.8 8.2.9 Standard...
8.1 Electronic temperature recorder (1) Specifications ● Model DER9601A (Applicable models:LXE10E- ● Power supply AC13V 50/60Hz ● Recording temperature range –30.0 to +25.0 °C A7,A11,A20,A26(A),A18(A,B) (–22 to +77˚F) and A30) ● Chart paper Round type 8-inch pressure- 8.1.1 Standard type...
Page 186
(2) Devices and schematic wiring diagram 2) Calibration function 1) Devices Calibration switch INC : To increase Device Location INC. temperature figure Temperature recorder board In the temperature recorder box OFF. ADJ. DEC : To decrease Recorder return air sensor (RRS) Evaporator suction area DEC.
8.1.2 Rechargeable battery type ●Temperature record with power supply turned off When the power supply is turned off, the pen will move to the outer circumference of recording sheet simultaneously. Power supply is turned off. ●Rechargeable battery The rechargeable battery is equipped on the electronic temperature recorder.
–3 –2 –1 DECOS DAIKIN ELECTRONICCONTAINER OPERATION SYSTEM Operation key ① SUPPLY LED (Lights when "supply air temperature" is indicated.) ⑦ IN RANGE LED (Lights when the control temperature is in range.) ② RETURN LED (Lights when "return air temperature" is indicated.) ⑧...
Page 189
2. Operation procedure flow chart When no power supply ※ 3 Battery mode, Operation Condition Setting with back-up battery (Set Point Temperature˚C / Humidity %, / Defrost Interval) Power OFF Non operation for 30 sec. Circuit Breaker ON Circuit Breaker OFF...
Page 190
Display (LED) off/ AUTOMATIC PUMP DOWN OPERATION mode The controller display (LED) to off and automatic pump down operation collecting refrigerant to the liquid receiver are executed. All indication light on (for 3 sec.) Starting preparation (for 18 sec.) ※...
Page 191
Setting item LED panel LCD panel Setting method Current indication mode –– –– –– MODE ON, OFF diSPOFF Select ON by using key, and press Display (LED) off key to determine the setting. MODE MODE Automatic pump ON, OFF P down Select "ON"...
–3 –2 –1 DECOS DAIKIN ELECTRONICCONTAINER OPERATION SYSTEM Operation key ① SUPPLY LED (Lights when "supply air temperature" is indicated.) ⑦ IN RANGE LED (Lights when the control temperature is in range.) ② RETURN LED (Lights when "return air temperature" is indicated.) ⑧...
Page 193
2 Operation procedure flow chart When no power supply ※ 3 Battery mode, Operation Condition Setting with back-up battery (Set Point Temperature˚C / Humidity %, / Defrost Interval) Power OFF Non operation for 30 sec. Circuit Breaker ON Circuit Breaker OFF...
Page 194
3. G-SET operation/Automatic pump down operation mood/Dehumidification ON-A・OFF setting The energy consunption reducing operation during G-SET operation, automatic pump down operation collecting refrigerant to the liquid receiver and dehumidification ON-A・OFF setting are executed. All indication light on (for 3 sec.)
Page 195
Setting item LED panel LCD panel Setting method Current –– –– –– indication mode MODE ON, OFF diSPOFF Select "ON" by using key, and G-SET press the key to operation determine the setting. MODE MODE ON, OFF P down Select "ON"...
Page 196
4. Setting flow chart This configuration setting flow shall be utilized, when Case 1) Where USDA cool transportation setting, defrosting interval automatic changing function, or dehumidification control clearing function is required. (Optional function setting) Case 2) Where an urgent change of container ID to other ID should be made.
Page 197
4.1 Controller initial setting Optional function mode ● ● USDA sensor setting Defrosting interval automatic changing ● Page 3-26 Dehumidification control on/off setting function on/off setting ● Dehumidification control clearing function on/off setting Basic function setting mode ●Controller type ●Logging interval...
Page 198
4.2. Optional function setting mode Following functions can be set up. With/Without setting of USDA sensor, With/without setting of cargo temperature, With/Without setting of dehumidification control, ON/OFF setting of defrosting interval automatic changing function, and ON/OFF setting of dehumidification control clearing function <Key operation to enter/exit>...
Page 199
<Key operation in this mode> Whenever the key is pressed, the display changes. Turn the power breaker OFF after the setting. To set the USDA ON/OFF and CARGO TEMPERATURE SENSOR ON/OFF: Select "OFF (not in use)", "3 (3 USDA probes are in use)", or "4 (3...
Page 200
5. Automatic pump down An automatic pump down system is applied to the unit to prevent the unit operation from extra decreasing of low pressure due to pump down operation or burning of scroll compressor due to close stop valve.
Page 201
6. Frozen mode 6.1 Control state transition and common control Thermostat ON (Pull-down range) ●Compressor Running ●Evaporator fan Low speed (L) Continuous compressor running for ≤ ≤ 2 minutes or more and RS SP - 0.5˚C ≤ RS > SP + 0.5˚C ≤...
Page 202
6.3 Set point temperature and control sensor When the set point temperature (referred to as SP hereafter) is –10.1˚C(+13.8˚F) or lower, the compressor is operated ON and OFF, in response to return air temperature. 6.4 Control qWhen the control temperature reaches SP-0.5˚C (point A), the compressor and condenser fan are turned off after the −10℃...
Page 203
7. Defrosting operation (1) Defrosting system A hot-gas defrost system is adopted in the units; i.e. the high temperature and high pressure refrigerant (hot gas) from the compressor is sent to the evaporator and drain pan for defrosting. Since the evaporator is heated directly by the hot gas (refrigerant), defrosting can be performed effectively.
Page 204
(4)Defrosting Interval Automatic Changing Function What is the Defrosting Interval Automatic Changing Function? This is a function to measure the time required for defrosting operation with the "long timer"and, according to the measurement, changes intervals of the defrosting operation. If a lapse of time after...
–3 –2 –1 DECOS DAIKIN ELECTRONICCONTAINER OPERATION SYSTEM Operation key ① SUPPLY LED (Lights when "supply air temperature" is indicated.) ⑦ IN RANGE LED (Lights when the control temperature is in range.) ② RETURN LED (Lights when "return air temperature" is indicated.) ⑧...
Page 206
2. Operation procedure flow chart When no power supply ※ 3 Battery mode, Operation Condition Setting with back-up battery (Set Point Temperature˚C / Humidity %, / Defrost Interval) Power OFF Non operation for 30 sec. Circuit Breaker ON Circuit Breaker OFF...
Page 207
3. G-SET operation/Automatic pump down operation mood/Dehumidification ON-A・OFF setting The energy consunption reducing operation during G-SET operation, automatic pump down operation collecting refrigerant to the liquid receiver and dehumidification ON-A・OFF setting are executed. ※ Dehumidfication control is available on A26 and A26A only.
Page 208
Setting item LED panel LCD panel Setting method Current –– –– –– indication mode MODE ON, OFF diSPOFF Select "ON" by using key, and G-SET press the key to operation determine the setting. MODE MODE ON, OFF P down Select "ON"...
8.2.4 Special controller setting (Applicable models:LXE10E-A23(A,B)) 1.Setting flow chart This configuration setting flow shall be utilized, when CASE 1) USDA transportation setting is required (※10 Optional Function Setting on page 3-29) CASE 2) Container ID shall to be subjected to change from another container for emergency use.
Page 211
2. Basic function setting mode <Key operation to enter/exit> Power OFF Circuit Breaker ON Circuit Breaker OFF after setting change Unit OFF OFF when no setting changed) I/O ON I/O OFF All indication lights on (for 3 sec.) for 3 sec.
Page 212
To set the power input: Select "Sing" or "dUAL" on the LED when the LCD displays "OC-SET" . Whenever the key is pressed, the indication of "Sing" or "dUAL" is INPUT POWER changed. Press the key to determine the setting.
8.2.5 Setting temperature and operation mode (Applicable models:LXE10E-A11,A12(A,B),A14,A15(A,B),A17(A),A27,A28 and A35(A)(with Partial frozen mode)) Operating temperature Operation mode Chilled mode Partial frozen mode Frozen mode Operation Set the operating Set the operating Set the operating temperature to the procedure temperature to the temperature to the range range of -10.1 to -30.0°...
8.2.6 Defrost interval (Applicable models:LXE10E-A6,A12(AtoE) andA28) Unlike standard units, this unit makes selection of the long-period setting timer or the short-period setting timer in accordance with a lapse of time after the unit starts up. ●Commencement of defrost operation...
8.2.7 G-SET operation 1 (Applicable models:LXE10E-A11,A20,A26(AtoC),A18(A,B),A30 and A35(A,B)) Generator setting operation MODE qPress the MODE key. wSelect "11", "12", "13", "14", "15" (kVA) or "OFF" indicated on the LED display using the key or key, and press the key to determine the setting, then the energy saving operation starts so that the energy consumption is saved to be the selected value (kVA) or lower.
8.2.9 Valve mode (Applicable models:LXE10E-A14 and A15(A,AR,B)) *Reheat coil and humidity sensor (optional) are required. The valve mode shown below is used for transportation of bulbs. To execute the valve mode, setup of the controller is required. (See the next page) In the valve mode operation, "b"is displayed in the first segment of the LED display.
Page 217
4. MODE OPERATION G-SET MODE Press the key (or key) in current indication mode to go to MODE operation. All indication Lights on (for 3 sec.) Starting Preparation (for 18 sec.) Current indication (Operation state) MODE MODE OPERATION In mode operation, the following settings/operations are available.
8.2.10 Dehumidification control (Applicable models:LXE10E-A11,A20,A26(AtoC),A14,A15(A,AR,B), A18(A,B), A27(A,B),A30,A31(A,B) and A33) 1. Summary ※If reheat coil (Optional) is equipped: The unit have dehumidification control by a reheat coil, which is under the evaporator coil. In dehumidification, the Reheat Solenoid Valve (RSV) opens to give high pressurized refrigerant to reheat coil.
Page 219
2. Names of components 2.1 Outside Trans FRESH q Reheat coil solenoid valve (RSV) 8-36...
Page 221
3. Dehumidification control setting This unit features the dehumidification function. Therefore, it is necessary to set whether the dehumidification control is to be executed or not according to the cargo to be transferred. You can set whether the dehumidification control is to be executed or not by operating the display panel of controller.
8.2.11 Manual check selection mode (Applicable models:LXE10E-A18(A,B) and A30) 1. Setting flow chart The LED indicate the values of following items. Compressor operating time, Evaporator fan motor high-speed running current, Evaporator fan motor low-speed running current, Condenser fan motor running current, Battery life, Horse power, Elapsed time after trip start, Evaporator fan motor running time, Condenser fan motor running time, Controller software version and sensor calibration.
8.2.12 F.PTI specification (Applicable models:LXE10E-A12(AtoE) and A28) In order to perform F.PTI operation, this unit is designed by adding the following ① to ④ functions to the standard specification, which are enclosed with a dotted rectangular as shown below.
Page 224
③List of detail on display and alarms of F.PTI step Step Item Alarm display Outside outdoor temperature J501 condition Check the pull-down period to reach 0° C J502 Pull-down period -exceeded- Check the chilled operation for controllability. Outside commencement condition of...
The battery is installed to the lid of the controller. The battery is positioned on CPU & I/O box in controller box. Rechargeable: DAIKIN original rechargeable battery 1. Function This battery is used without main power supply for the following functions.
8.3 Control box (Applicable models:LXE10E-A6,A11,A20,A26(A), A12(AtoE),A28,A17(A) and A35(A)) 8.3.1 Installation of personal computer receptacle and spare fuse in the control box ●Inside of the control box 1 Personal computer receptacle 2 Fuse holder/Spare fuse 8-43...
8.3.2 Cable clamp bracket 1 (Applicable models:LXE10E-A6,A12(A,B),A28, A18(A,B) and A30) cable clamp When it is operated on the trailer or railway chassis, be sure to fasten the power cable with CABLE CLAMP LOOSE CLAMP Patching clasp 8-44...
8.3.3 Cable clamp bracket 2 (Applicable models:LXE10E-A5(BR),A7,A8,A9, A11,A20,A26(A),A12(AtoE),A28,A17(A),A35(A),A19, and A26(B,C)) cable clamp When it is operated on the trailer or railway chassis, be sure to fasten the power cable with CABLE CLAMP POWER CABLE 8-45...
Type of USDA sensor should be set. 8.4.3 USDA sensor calibration USDA requires sensor calibration every transportation and report each offset figure. Free-supply downloading software enable to assist this. Please refer to "Operation manual for Daikin Container Communication Software". 8.4.4 USDA transportation requirement Cargo and refrigeration unit shall be required pre-cooling before cargo loading.
Page 230
●USDA receptacle USDA sensor receptacle Cargo temperature sensor receptacle Parsonal computer port receptacle ●USDA sensor Connect to receptacle 8-47...
8.5 TransFRESH (Applicable models:LXE10E-A9,A18(A,B),A30 and A27(A,B)) Attachment for the TransFRESH CA devices are provided to control the internal atmosphere (quantity of O and CO Use the CA devices according to the Operation Manual supplied by TransFRESH. The controller and sensor included in the CA devices are installed by the TransFRESH's agents before each transportation.
Page 232
●An example of installation of CA devices, inside q TransFRESH ASS'Y A4&A5 CABLES W/MOUNTING BOX 8-49...
8.6 Special service port (Applicable models:LXE10E-A23(A,B)) 8.6.1 Collection of refrigerant qWhen release the refrigerant from the CAUTION refrigerant system, be sure to use a refrigerant recovery unit to protect the ozone 1. Use the pressure indicating function layer around the earth from depletion.
Page 234
●Caution on the service work qBe sure not to bend the refrigerant pipe when turning the hose joint. Gauge manifold wThe remaining pressure in the charge hose may cause installation failure. In this case, Passage open- try it again after relieving the pressure in /closing cock the hose.
8.7 Pressure gauge (Applicable models:LXE10E-A23(A,B)) TYPE : GV55-DO2 Low pressure gauge is fitted in this model. Pressure gauge piping Flare nut of pressure gauge piping Low pressure gauge Pressure gauge piping When the flare nut of pressure gauge piping is loosened for replacing pressure gauge, "LOCTITE"...
Page 236
Be sure to clamp the pressure gauge piping to suction piping using "Tie wrap" at the following part. Tie wrap "Tie wrap" Tie wrap After installing insulation material on suction pipe, clamp the pressure gauge piping to suction piping together using "Tie wrap".
Need help?
Do you have a question about the LXE10E-A and is the answer not in the manual?
Questions and answers
Hi , "Please inform me where in the official Daikin information I can find the following description, especially regarding the overhaul recommendations. Thank you. "For Daikin LXE10E-A series reefer units, it is generally recommended to perform a major overhaul every 40,000 running hours. Additionally, a minor overhaul should be conducted every 20,000 running hours. These intervals help ensure optimal performance and prevent unexpected breakdowns."
Refer to the *Daikin Container Refrigeration Unit Service Manual* for the LXE10E-A series. This manual provides necessary information on operation, functions, and maintenance, including overhaul recommendations.
This answer is automatically generated
Hi Anderson, because I can't find the overhaul recommendations in Service Manual* for the LXE10E-A series., please kindly advise where the overhaul recommendations from the content 1 to content 8 in Service Manual* for the LXE10E-A series. Thanks for your assistance.
здравствуйте не вижу в схеме (ТРВ)