4. MODE OPERATION
MODE
M
Press the
key (or
All indication
Lights on
(for 3 sec.)
Starting
Preparation
(for 18 sec.)
Current
indication
(Operation state)
MODE
M
MODE
OPERATION
In mode operation, the following settings/operations are available.
1. Generator setting
Total power consumption can be reduced to desired Max setting for the specific generators set or
power facilities.
The selections are "off (No limit)", "15" "14" "13" "12" "11" KVA.
2. Automatic pump down
Pump down can be executed automatically.
(Refer to "Automatic pump down" in 4.1.3)
3. LED display Light-OFF(OPTION)
All LED (includes LED lamp)can be switched off.
In order to execute this function,initial setting (Refer to initial setting in section 3.8.3) shall be required
to change"on" position in advance.
4. Valve mode setup
In this mode, the valve mode operation can be executed. (See "Valve mode" in P.5-33.)
If the valve mode is set to "On", the initial setup can be changed as shown below.
q Dehumidification: on/off (default)
If "on" is chosen, the inside humidity can be changed from 95% (default) to 60%.
Default: 95%
w Evaporator fan speed: (H/L) alternate operation (default)/High/Low
e Defrost start temperature (RS): From +4˚C to +18˚C, default: 5˚C
G-SET
key) in current indication mode to go to MODE operation.
8-34