● Automatic PTI enable conditions
Water cooled
operation
S. PTI
F. PTI
M. CHECK

3.9.2.2 Short PTI (S.PTI)

● Step display and content
Step
Basic data record (container No., date,
P00
time, compressor integrated run-hour,
ambient temperature)
P02
Alarm check on all sensors
P04
Power conditions (voltage and frequency) check
P05
Compressor start running check
Actuating pressure check at OFF and
P06
ON of High pressure switch (HPS)
P08
Pump-down check
Solenoid valve leakage check
•Liquid solenoid valve (LSV)
•Injection solenoid valve (ISV)
P10
•Hot gas solenoid valve (HSV)
•Defrost solenoid valve (DSV)
•Discharge gas by-pass (BSV)
•Economizer solenoid valve (ESV)
Supply and return air sensor (SS and RS)
P12
accuracy check
Pressure sensor (HPT and LPT)
P14
accuracy check
Evaporator fan high and low-speed
P16
operation check
P18
Start up
Economizer solenoid valve (ESV)
P20
opening or closing check
Discharge gas by-pass solenoid valve
P22
(BSV)opening or closing check
Defrost solenoid valve (DSV)
P24
opening or closing check
P26
Standard pull-down operation
Suction modulating valve (SMV) operation
P28
check
Electronic expansion valve (EV)
P29
operation check
Injection solenoid valve (ISV) opening
P30
or closing check
Hot-gas 3-way solenoid valve (HSV) and Reheat coil solenoid
P32
valve (RSV -optional) opening or closing check
※1 If the ambient temp is –10˚C or lower, the function check of the solenoid valve cannot be preformed
correctly, short circuit the terminals 121 and 102 on the terminal board, and check the operation of
the solenoid valve.
※2 If the difference between ambient temperature and return air temperature is 15˚C or higher, these
steps will be skipped.
Air cooled
operation
–10˚C < Ambient temperature ≦ 43˚C
When the ambient temperature is above 43˚C or below –10˚C, the correct judgment
may not be possible.
–10˚C ≦ Ambient temperature ≦ 43˚C
When the ambient temperature is above 43˚C or below -10˚C, the following alarm will be indicated.
J501: Out of ambient temperature specified conditon.
Content
※1 ※2
※2
※2
3-56
Ambient temperature condition
● S.PTI Flow chart operation
UNIT ON/OFF key: on
N
Select S.PTI
within 18 seconds
S.PTI start
P00 through P32
Y
Compressor protective
device activation
N
PTI data logging
S.PTI termination
Normal operation
Forced termination