H6-00 - Outdoor Unit: Malfunction Of Position Detection Sensor - Daikin RXM20R Service Manual

Hide thumbs Also See for RXM20R:
Table of Contents

Advertisement

3.5.20 H6-00 – Outdoor unit: Malfunction of position detection sensor
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Compressor fails to start
within 15 seconds after
the compressor run
command signal is sent.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the compressor. See "4.2 Compressor" [
Possible cause: Faulty compressor or miswiring of the compressor power
supply cable.
2 Perform a check of the main PCB. See
Possible cause: Faulty main PCB.
3 Check that all stop valves of the refrigerant circuit are open. See
"5.2 Refrigerant
circuit" [
Possible cause: Closed stop valve in the refrigerant circuit.
4 Check if the refrigerant circuit is clogged. See
Possible cause: Clogged refrigerant circuit.
5 Check if the refrigerant circuit is correctly charged. See
4
circuit" [
 207].
Possible cause: Refrigerant overcharge or shortage.
6 Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
Possible cause: Non‑condensables and/or humidity in the refrigerant circuit.
7 Check if the power supply is compliant with the regulations. See
4
circuit" [
 205].
Possible cause:
▪ Faulty or disturbance of the power supply (power supply MUST be within
range of nominal operating voltage ±4%),
▪ Power drop,
▪ Short circuit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Effect
Unit will NOT stop
operating.
If the error re-occurs
within 8 minutes: unit will
stop operating.
"4.12 Main
4
 207].
"5.2 Refrigerant
"5.2 Refrigerant
circuit" [
3
Troubleshooting
|
Reset
Automatic reset after a
continuous operation of
10 minutes.
Manual reset via user
interface.
4
 57].
4
PCB" [
 125].
4
circuit" [
"5.2  Refrigerant
4
 207].
"5.1 Electrical
Service manual
 207].
31