4. Setting flow chart
This configuration setting flow shall be utilized, when
Case 1) Where USDA cool transportation setting, defrosting interval automatic changing function, or
dehumidification control clearing function is required. (Optional function setting)
Case 2) Where an urgent change of container ID to other ID should be made.
(Setting of container ID and calendar)
Case 3) Where a new controller is installed for replacement. (Settings of optional function, basic
function, optional conditions, and input data should be made.)
NOTE 1 : All initial settings are pre-setted, when the unit is delivered.
2 : In case to complete the setting change, CIRCUIT BREAKER shall be turned off
Power OFF
Circuit Breaker ON
Unit OFF
I/O ON
All lights on
(for 3 sec.)
for 3 sec.
for 3 sec.
Preparation
(for 18 sec.)
USDA: OFF (or 3 or 4)
S
dHU: OFF (or ON)
S
AUT-INT: ON (or OFF)
S
dHU-CAN: ON (or OFF)
CASE 1
for 3 sec.
Optional
PTI
Function
Setting
DECOS3: D (C or B or A)
S
Log. Interval: 30 (or 15 or 60 or 120)
S
REC SEN: ON (or OFF)
S
OC-SET: Sing (or Dual)
S
HP: 10 (or 5)
S
DISP: OFF (or ON)
S
COMP: 100 (or 33)
S
REHEAT: OFF (or ON)
S
FA-SEN: OFF (H or L)
(only for DESCOS3d)
CASE 3 (Refer to 3.8.3 of Service manual)
Circuit Breaker OFF
after setting change
(
I/O
OFF when no setting changed)
for 3 sec.
for 3 sec.
Basic
Function
Setting
CHARTLS: OFF (or ON)
S
USDA 1/2: 2 (or 1)
S
H001~H006
S
d-1**~d-2**
S
C/F : C (or F)
8-13
for 3 sec.
Optional
Container
Condition
I.D & Time
Setting
Setting
Container I.D
S
Controller
Time
CASE 2