8.2.5 Setting temperature and operation mode
(Applicable models:LXE10E-A11,A12(A,B),A14,A15(A,B),A17(A),A27,A28
and A35(A)(with Partial frozen mode))
Operation mode
Chilled mode
Operation
Set the operating
procedure
temperature to the
DECOSⅢc
range of +30 to -2.9° C
(+86 to +26.8<).
Operation
Set the operating
procedure
temperature to the
DECOSⅢd
range of +30 to -3.0° C
(+86 to +26.6<).
Functions
Used to perform chilled
operation, which
proportionally controls
the temperature inside
by means of the
sensor of discharge air
temperature.
The evaporation fan performs High-operation.
Operating temperature
Partial frozen mode
Set the operating
temperature to the range
of -3.0 to -10.0° C (+26.6
to +14<).
Set the operating
temperature to the range
of -3.1 to -10.0° C (+26.4
to +14<).
Used to perform partial
frozen operation, which
proportionally controls the
temperature inside by
means of the sensor of
suction air temperature.
8-30
Frozen mode
Set the operating temperature to the
range of -10.1 to -30.0° C (+13.8 to -
22<).
Set the operating temperature to the
range of -10.1 to -30.0° C (+13.8 to -
22<).
Used to perform frozen operation,
which turns the compressor ON or
OFF and proportionally controls the
temperature inside by means of the
sensor of suction air temperature.
The evaporation fan performs Low-operation.