Daikin LXE10E-A Service Manual page 157

Marine type container refrigeration unit
Table of Contents

Advertisement

https://daikin-p.ru
Alarm
E303
Humidity setting request
E305
Defrost timer setting request
E307
Calendar setting request
E311
Trip start setting request
E401
Supply air temperature sensor (SS) fault
E402
Data recorder supply air temperature sensor (DSS) fault
E403
Return air temperature sensor (RS) fault
E404
Data recorder return air temperature sensor (DRS) fault
E405
Discharge pipe temperature sensor (DCHS) fault
E406
Suction gas temperature sensor (SGS) fault
E407
Evaporator inlet pipe temperature sensor (EIS) fault
E409
Evaporator outlet pipe temperature sensor (EOS) fault
E411
Ambient temperature sensor (AMBS) fault
E413
Low pressure transducer (LPT) fault
E415
High pressure transducer (HPT) fault
E419
Voltage sensor (PT2) fault
E425
Pulp temperature sensor (USDA1) fault
E427
Pulp temperature sensor (USDA2) fault
E429
Pulp temperature sensor (USDA3) fault
E431
Humidity sensor (Hus) fault
E433
Carge temperature sensor (STS) fault
E417
Voltage sensor (PT1) fault
E421
Current sensor (CT1) fault
E423
Current sensor (CT2) fault
E603
Disconnection of suction modulating valve (SMV) or faulty
driving circuit or wrong setting of controller
E607
Faulty contact point of manual defrost key (sheet key)
E707
Momentary power failure
E807
Opened lower ventilator
Content
6-15
Possible cause/checkpoint
System malfunctioned
・Faulty controller
Faulty operation
・Wrong initial setting of controller
System malfunction
・Faulty sensor
・Faulty controller
・Broken or short-circuited lead wire
・Wrong wiring
・Disconnection of connector
Malfunctioned equipment
・Faulty sensor
・Faulty controller
・Broken or short-circuited lead wire
・Wrong wiring
・Disconnection of connector
Malfunctioned equipment
・Faulty controller
・Faulty SMV coil
・Faulty PCB for SMV
・Broken wire of harness (disconnection of connector)
Faulty operation
・Wrong initial setup of controller
Faulty short-circuit of switch
Faulty short-circuit of CPU
The power is not supplied for 40 to 300 mm sec.
The lower ventilator is opened during frozen operation