Wiring Configuration For An External Alarm Reset; Wiring Configuration For Speed Reference Using A Manual Potentiometer - Danfoss VLT HVAC Drive FC 102 Design Manual

355–1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Application Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
29
D IN
D IN
32
D IN
33
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 12.7 Wiring Configuration for Start/Stop with Reversing
and 4 Preset Speeds
12
12
210
®
VLT
HVAC Drive FC 102
Parameters
Function
Setting
Parameter 5-10 T
[8] Start
erminal 18
Digital Input
Parameter 5-11 T
[10]
erminal 19
Reversing*
Digital Input
Parameter 5-12 T
[0] No
erminal 27
operation
Digital Input
Parameter 5-14 T
[16] Preset ref
erminal 32
bit 0
Digital Input
Parameter 5-15 T
[17] Preset ref
erminal 33
bit 1
Digital Input
Parameter 3-10 P
reset Reference
Preset ref. 0
25%
Preset ref. 1
50%
Preset ref. 2
75%
Preset ref. 3
100%
*=Default value
Notes/comments:
Danfoss A/S © 11/2017 All rights reserved.
12.4 Wiring Configuration for an External
Alarm Reset
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 12.8 Wiring Configuration for an External Alarm Reset
12.5 Wiring Configuration for Speed
Reference Using a Manual
Potentiometer
FC
+10 V
50
A IN
53
≈ 5kΩ
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 12.9 Wiring Configuration for Speed Reference
(Using a Manual Potentiometer)
Parameters
Function
Setting
Parameter 5-11 T
[1] Reset
erminal 19
Digital Input
*=Default value
Notes/comments:
Parameters
Function
Setting
Parameter 6-10 T
0.07 V*
erminal 53 Low
Voltage
Parameter 6-11 T
10 V*
erminal 53 High
Voltage
Parameter 6-14 T
0 RPM
erminal 53 Low
Ref./Feedb. Value
Parameter 6-15 T
1500 RPM
erminal 53 High
Ref./Feedb. Value
*=Default value
Notes/comments:
MG16C302