Danfoss VLT HVAC Drive FC 102 Design Manual page 61

355–1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Specifications
®
VLT
HVAC Drive FC 102
Normal overload
(Normal overload=110% current during 60 s)
Typical shaft output at 550 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 550 V) [A]
Intermittent (60 s overload) (at 550 V) [A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload) (at 575/690 V) [A]
Continuous kVA (at 550 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 550 V) [A]
Continuous (at 575 V) [A]
Continuous (at 690 V) [A]
Maximum number and size of cables per phase
2
- Motor [mm
(AWG)]
- Mains [mm
2
(AWG)] (F12)
2
- Mains [mm
(AWG)] (F13)
- Brake [mm
2
(AWG)]
Maximum external mains fuses [A]
Estimated power loss at 600 V [W]
Estimated power loss at 690 V [W]
Maximum added losses for circuit breaker or disconnect and contactor
[W], (F13 only)
Maximum panel options losses [W]
Efficiency
3)
Output frequency [Hz]
Control card overtemperature trip [°C (°F)]
Table 7.12 Electrical Data for Enclosures F12/F13, Mains Supply 6x525–690 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.5 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.12 Efficiency. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
MG16C302
Design Guide
1)
2), 3)
2), 3)
Danfoss A/S © 11/2017 All rights reserved.
P1M0
NO
850
1150
1000
F12/F13
1108
1219
1060
1166
1056
1056
1267
1068
1022
1022
12x150 (12x300
12x150 (12x300
mcm)
8x240 (8x500 mcm)
8x240 (8x500 mcm)
8x456 (8x900 mcm)
8x456 (8x900 mcm)
6x185 (6x350 mcm)
6x185 (6x350 mcm)
1600
13731
14250
665
400
0.98
0–500
85 (185)
± 15% (tolerance relates to variety in voltage and cable conditions). These
P1M2
P1M4
NO
NO
1000
1100
1350
1550
1200
1400
F12/F13
F12/F13
1317
1479
1449
1627
1260
1415
1386
1557
1255
1409
1255
1409
1506
1691
1269
1425
1214
1364
1214
1364
12x150 (12x300
mcm)
mcm)
8x240 (8x500
mcm)
8x456 (8x900
mcm)
6x185 (6x350
mcm)
2000
2500
16190
18536
16821
19247
863
1044
400
400
0.98
0.98
0–500
0–500
85 (185)
85 (185)
7
7
59