Wiring Configuration: External Alarm Reset - Danfoss VLT HVAC Drive FC 102 Operating Manual

110-800 kw, enclosures d9h-d10h and e5h-e6h
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Operating Guide | VLT® HVAC Drive FC 102
Table 63: Wiring Configuration for Start/Stop with Reversing and 4 Preset Speeds
+24 V
XD2.10
+24 V
XD2.11
D IN
XD2.12
D IN
XD2.13
COM
XD2.18
D IN
XD2.14
D IN
XD2.15
D IN
XD2.16
D IN
XD2.17

8.1.7 Wiring Configuration: External Alarm Reset

Table 64: Wiring Configuration for External Alarm Reset
+24 V
XD2.10
+24 V
XD2.11
D IN
XD2.12
D IN
XD2.13
COM
XD2.18
D IN
XD2.14
D IN
XD2.15
D IN
XD2.16
D IN
XD2.17
D IN
XD2.19
Danfoss A/S © 2018.10
Parameters
Function
Parameter 5-10 Terminal 18 Digital Input
Parameter 5-11 Terminal 19 Digital Input
Parameter 5-12 Terminal 27 Digital Input
Parameter 5-14 Terminal 32 Digital Input
Parameter 5-15 Terminal 33 Digital Input
Parameter 3-10 Preset Reference
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 18 in the parameter title corresponds to terminal XD2.12 in the control compartment.
Terminal 19 in the parameter title corresponds to terminal XD2.13 in the control compartment.
Terminal 27 in the parameter title corresponds to terminal XD2.14 in the control compartment.
Terminal 32 in the parameter title corresponds to terminal XD2.16 in the control compartment.
Terminal 33 in the parameter title corresponds to terminal XD2.17 in the control compartment.
Parameter
Function
Parameter 5-11 Terminal 19 Digital Input
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 19 in the parameter title corresponds to terminal XD2.13 in the control compartment.
Wiring Configuration Examples
Setting
[8] Start
[10] Reversing*
[0] No operation
[16] Preset ref bit 0
[17] Preset ref bit 1
Preset ref. 0 = 25%
Preset ref. 1 = 50%
Preset ref. 2 = 75%
Preset ref. 3 = 100%
Setting
[1] Reset
AQ262141314214en-000101 / 130R0880 | 119

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents