Advertisement

Product Features
Example with varying flow over 1 year
Illustration 5.11 is based on pump characteristics obtained from a pump datasheet. The result obtained shows energy
savings more than 50% at the given flow distribution over a year. The payback period depends on the price per kWh and
the price of the drive. In this example, it is less than a year when compared with valves and constant speed.
[h]
t
2000
1500
1000
5
5
500
Illustration 5.11 Flow Distribution Over 1 Year
m
3
/h
350
300
250
200
150
100
Σ
Table 5.2 Energy Savings Calculation
28
100
200
300
400
Distribution
%
Hours
Power
A
-B
1
5
438
42.5
15
1314
38.5
20
1752
35.0
20
1752
31.5
20
1752
28.0
20
1752
23.0
100
8760
Danfoss A/S © 11/2017 All rights reserved.
®
VLT
HVAC Drive FC 102
Q
[m
3
/h]
Valve regulation
Consumption
kWh
1
18615
50589
61320
55188
49056
40296
275064
Drive control
Power
Consumption
A
-C
kWh
1
1
42.5
18615
29.0
38106
18.5
32412
11.5
20148
6.5
11388
3.5
6132
26801
MG16C302