Danfoss VLT HVAC Drive FC 102 Design Manual page 177

355–1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Electrical Installation Con...
Analog input/output terminals
Terminal
Parameter
53
Parameter
Reference
group 6-1*
Analog Input 1
54
Parameter
Feedback
group 6-2*
Analog Input 2
55
Table 10.9 Analog Input/Output Terminal Descriptions
Relay terminals:
RELAY 1
01
02 03
Illustration 10.13 Relay 1 and Relay 2 Terminals
Relay 1 and relay 2. The location of the outputs
depends on the drive configuration. See the
operating guide.
Terminals on built-in optional equipment. See the
instructions provided with the equipment option.
10.4.3 Input Polarity of Control Cables
PNP (Source)
Digital input wiring
12
13
18
19
27
Illustration 10.14 Input Polarity of Control Terminals (PNP
Source)
MG16C302
Design Guide
Default
Description
setting
Analog input. For
voltage or current.
Switches A53 and
A54 select mA or V.
Common for analog
input.
RELAY 2
04
05 06
29
32
33
20
37
Danfoss A/S © 11/2017 All rights reserved.
NPN (Sink)
Digital input wiring
12
13
18
19
27
Illustration 10.15 Input Polarity of Control Terminals (NPN
Sink)
NOTICE
Use shielded cables to comply with EMC emission specifi-
cations. For more information, see chapter 10.16 EMC-
compliant Installation.
Illustration 10.16 Shield Termination and Strain Relief of
Control Cable
29
32
33
20
37
175
10
10

Advertisement

Table of Contents
loading

Table of Contents