10.15.2 Emission Requirements
According to the EMC product standard for adjustable speed drives EN/IEC 61800-3:2004, the EMC requirements depend on
the environment in which the drive is installed. These environments along with the mains voltage supply requirements are
defined in Table 10.40.
The drives comply with EMC requirements described in IEC/EN 61800-3 (2004)+AM1 (2011), category C3, for equipment
having greater than 100 A per-phase current draw, installed in the second environment. Compliance testing is performed
with a 150 m (492 ft) shielded motor cable.
Category
Definition
(EN 61800-3)
C1
First environment (home and office) with a supply voltage less than 1000 V.
C2
First environment (home and office) with a supply voltage less than 1000 V, which
is not plug-in or movable and where a professional is intended to be used to
install or commission the system.
C3
Second environment (industrial) with a supply voltage lower than 1000 V.
C4
Second environment with the following:
Supply voltage equal to or above 1000 V.
Rated current equal to or above 400 A.
Intended for use in complex systems.
Table 10.40 Emission Requirements
When the generic emission standards are used, the drives are required to comply with Table 10.41.
Environment
Generic standard
First environment
EN/IEC 61000-6-3 Emission standard for residential, commercial,
(home and office)
and light industrial environments.
Second environment
EN/IEC 61000-6-4 Emission standard for industrial environments.
(industrial environment)
Table 10.41 Generic Emission Standard Limits
10.15.3 Immunity Requirements
The immunity requirements for drives depend on the installation environment. The requirements for the industrial
environment are higher than the requirements for the home and office environment. All Danfoss drives comply with the
requirements for both the industrial and the home/office environment.
To document immunity against burst transient, the following immunity tests have been performed on a drive (with options
if relevant), a shielded control cable, and a control box with potentiometer, motor cable, and motor. The tests were
performed in accordance with the following basic standards. For more details, see Table 10.42.
EN 61000-4-2 (IEC 61000-4-2): Electrostatic discharges (ESD): Simulation of electrostatic discharges from human
beings.
EN 61000-4-3 (IEC 61000-4-3): Incoming electromagnetic field radiation, amplitude modulated simulation of the
effects of radar, radio communication equipment, and mobile communications equipment.
EN 61000-4-4 (IEC 61000-4-4): Burst transients: Simulation of interference brought about by switching a contactor,
relay, or similar devices.
MG16C302
Design Guide
Danfoss A/S © 11/2017 All rights reserved.
Conducted emission (EN 55011)
Class B
Class A Group 1
Class A Group 2
No limit line.
An EMC plan must be made.
Conducted emission requirement
according to EN 55011 limits