Danfoss VLT HVAC Drive FC 102 Design Manual page 237

355–1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Appendix
Coil number
Description
1–16
Drive control word (see Table 14.14).
17–32
Drive speed or setpoint reference range 0x0–0xFFFF (-200% ... ~200%).
33–48
Drive status word (see Table 14.14).
49–64
Open-loop mode: Drive output frequency.
Closed-loop mode: Drive feedback signal.
65
Parameter write control (master-to-slave).
0 = Parameter changes are written to the RAM of the drive.
1 =Parameter changes are written to the RAM and EEPROM of the drive.
66–65536
Reserved.
Table 14.13 Coils and Holding Registers
Coil
0
01
Preset reference LSB
02
Preset reference MSB
03
DC brake
04
Coast stop
05
Quick stop
06
Freeze frequency
07
Ramp stop
08
No reset
09
No jog
10
Ramp 1
11
Data not valid
12
Relay 1 off
13
Relay 2 off
14
Set up LSB
15
Set up MSB
16
No reversing
Table 14.14 Drive Control Word (FC Profile)
Register
Description
number
00001–00006
Reserved.
00007
Last fault code from an FC data object interface.
00008
Reserved.
00009
Parameter index
00010–00990
000 parameter group (parameters 001–099).
01000–01990
100 parameter group (parameters 100–199).
02000–02990
200 parameter group (parameters 200–299).
03000–03990
300 parameter group (parameters 300–399).
04000–04990
400 parameter group (parameters 400–499).
...
...
49000–49990
4900 parameter group (parameters 4900–4999).
50000
Input data: Drive control word register (CTW).
50010
Input data: Bus reference register (REF).
...
...
50200
Output data: Drive status word register (STW).
50210
Output data: Drive main actual value register (MAV).
Table 14.16 Holding Registers
1) Used to specify the index number used when accessing an indexed parameter.
MG16C302
Design Guide
1
No DC brake
No coast stop
No quick stop
No freeze frequency
Start
Reset
Jog
Ramp 2
Data valid
Relay 1 on
Relay 2 on
Reversing
1)
.
Danfoss A/S © 11/2017 All rights reserved.
Signal direction
Master-to-slave
Master-to-slave
Master-to-slave
Slave-to-master
Master-to-slave
Coil
0
33
Control not ready
34
Drive not ready
35
Coasting stop
36
No alarm
37
Not used
38
Not used
39
Not used
40
No warning
41
Not at reference
42
Hand mode
43
Out of frequency range
44
Stopped
45
Not used
46
No voltage warning
47
Not in current limit
48
No thermal warning
Table 14.15 Drive Status Word (FC Profile)
1
Control ready
Drive ready
Safety closed
Alarm
Not used
Not used
Not used
Warning
At reference
Auto mode
In frequency range
Running
Not used
Voltage warning
Current limit
Thermal warning
235
14
14