Danfoss VLT HVAC Drive FC 102 Design Manual page 59

355–1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Specifications
®
VLT
HVAC Drive FC 102
Normal overload
(Normal overload=110% current during 60 s)
Typical shaft output at 550 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 550 V) [A]
Intermittent (60 s overload) (at 550 V) [A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload) (at 575/690 V) [A]
Continuous kVA (at 550 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 550 V) [A]
Continuous (at 575 V) [A]
Continuous (at 690 V)
Maximum number and size of cables per phase
2
- Motor [mm
(AWG)]
- Mains [mm
2
(AWG)]
2
- Brake [mm
(AWG)]
Maximum external mains fuses [A]
Estimated power loss at 600 V [W]
Estimated power loss at 690 V [W]
Efficiency
3)
Output frequency [Hz]
Control card overtemperature trip [°C (°F)]
Table 7.10 Electrical Data for Enclosures F8/F9, Mains Supply 6x525–690 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.5 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.12 Efficiency. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
MG16C302
Design Guide
1)
2), 3)
2), 3)
Danfoss A/S © 11/2017 All rights reserved.
P450
P500
NO
NO
355
400
450
500
450
500
F8/F9
F8/F9
470
523
517
575
450
500
495
550
448
498
448
498
538
598
453
504
434
482
434
482
4x240 (4x500
4x240 (4x500
mcm)
mcm)
4x85 (4x3/0
4x85 (4x3/0
mcm)
mcm)
2x185 (2x350
2x185 (2x350
mcm)
mcm)
630
630
5323
6010
5529
6239
0.98
0.98
0–500
0–500
85 (185)
85 (185)
± 15% (tolerance relates to variety in voltage and cable conditions). These
P560
P630
NO
NO
450
500
600
650
560
630
F8/F9
F8/F9
596
630
656
693
570
630
627
693
568
600
568
627
681
753
574
607
549
607
549
607
4x240 (4x500
4x240 (4x500
mcm)
mcm)
4x85 (4x3/0
4x85 (4x3/0
mcm)
mcm)
2x185 (2x350
2x185 (2x350
mcm)
mcm)
630
630
7395
8209
7653
8495
0.98
0.98
0–500
0–500
85 (185)
85 (185)
57
7
7