Signals (Output Signals); Status Signals (Output Signals) - AUMA SG Series Operation Instructions Manual

Part-turn actuators with actuator controls mec 03.1 marine version
Table of Contents

Advertisement

SG 04.2
SG 10.2
with actuator controls MEC 03.1
11.

Signals (output signals)

11.1.

Status signals (output signals)

Up to 4 programmable semi-conductors or relay outputs are available, each with
max. 30 V/1 A switching power.
Table 16:
Exemplary assignment of 4 outputs
Designation of output contacts in wiring dia-
gram
K 1 = End position OPEN
K 2 = End position CLOSED
K 3 = Fault
K 4 = REMOTE
(only for version with local controls)
Signals (output signals)
Designation of output contact in AUMA CDT software
Signal DOUT 2 = End position OPEN
Signal DOUT 1 = End position CLOSED
Signal DOUT 3 = Fault
Signal DOUT 4 = Selector sw. REMOTE
39