This document contains information for installation, commissioning, operation and maintenance staff. It is intended to support device installation and commissioning. Reference documents: Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA (refer to <Addresses>). Table of contents Page Safety instructions.........................
Page 3
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Table of contents Operation..........................6.1. Manual operation 6.1.1 Manual operation: engage 6.1.2 Manual operation: disengage 6.2. Motor operation 6.2.1 Local operation 6.2.2 Actuator operation from remote Indications..........................7.1. Indication lights 7.2. Mechanical position indicator/running indication Signals.............................
Page 4
Features and functions of actuator controls 13.3. Service conditions 13.4. Further information Spare parts..........................14.1. Part-turn actuators SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 14.2. Actuator controls AUMA MATIC AM 01.1/AM 02.1 Certificates..........................15.1. Declaration of Incorporation and EC Declaration of Conformity Index............................Addresses..........................
Any device modification requires prior consent of the manufacturer. Range of application AUMA part-turn actuators are designed for the operation of industrial valves, e.g. butterfly valves and ball valves. Other applications require explicit (written) confirmation by the manufacturer.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Safety instructions AM 01.1 Escalators Continuous duty Buried service Permanent submersion (observe enclosure protection) Potentially explosive areas, with the exception of zone 22 Radiation exposed areas in nuclear power plants No liability can be assumed for inappropriate or unintended use. Observance of these operation instructions is considered as part of the device's designated use.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Safety instructions Indicates a potentially hazardous situation with a low level of risk. Failure to observe this warning may result in minor or moderate injury. May also be used with property damage. Potentially hazardous situation.
Wiring diagram Control Type and size These instructions apply to the following devices: Part-turn actuators for open-close duty: SG 05.1, 07.1, 10.1, 12.1 Part-turn actuators for modulating duty: SGR 05.1, 07.1, 10.1, 12.1 AM 01.1/02.1 = Actuator controls AUMA MATIC...
A part-turn actuator is an actuator which transmits a torque to the valve for less than one full revolution. It need not be capable of withstanding thrust. AUMA part-turn actuators are driven by an electric motor. A handwheel is provided for manual operation. Switching off in end positions may be either by limit or torque seating.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Transport, storage and packaging AM 01.1 Transport, storage and packaging Transport For transport to place of installation, use sturdy packaging. Hovering load! Risk of death or serious injury. Do NOT stand below hovering load. Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT to handwheel.
AM 01.1 Assembly Assembly Mounting position AUMA actuators and actuator controls can be operated without restriction in any mounting position. Ball handle: fit to handwheel To avoid damage during transport, the ball handle is fitted at the rear of the handwheel.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Assembly Fasten actuator with screws [4]. Information: We recommend glueing the screws using sealing material to avoid contact corrosion. Fasten screws [4] crosswise with a torque according to table: Table 2: Tightening torques for screws Screws Tightening torque T...
Page 14
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Assembly AM 01.1 Loosen 3 screws of the board, turn board to the new position and fasten the screws. Check whether O-ring is in good condition, correctly insert O-ring. Turn local controls into new position and re-place. Cable damage due to twisting or pinching! Risk of functional failures.
The pertaining wiring diagram/terminal plan (in German and English language) is plan attached to the device in a weather-proof bag, together with these operation instructions. It can also be obtained from AUMA (state commission no., refer to name plate) or downloaded directly from the Internet (www.auma.com). Protection on site For short-circuit protection and for disconnecting the actuator from the mains, fuses and disconnect switches have to be provided by the customer.
PE connection : max. 6 mm² flexible/10 mm² solid Control contacts (1 to 50): max. 2.5 mm² 5.2.1 Terminal compartment: open Figure 10: Connection AUMA plug/socket connector, version S Cover Screws for cover O-ring Screws for socket carrier Socket carrier...
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Electrical connection Hazardous voltage! Risk of electric shock. Disconnect device from the mains before opening. Loosen screws [2] and remove cover [1]. Loosen screws [4] and remove socket carrier [5] from cover [1]. Insert cable glands [8] suitable for connecting cables.
Page 18
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Electrical connection AM 01.1 In case of a fault: Hazardous voltage while protective earth conductor is NOT connected! Risk of electric shock. Connect all protective earth conductors. Connect PE connection to external protective earth conductor of connecting cables.
Permissible length of connecting cables: max. 100 m. Observe prior to If the actuator is equipped with a position transmitter (RWG): Connecting cables connection must be designed as shielded version. Versions with potentiometer in the actuator are not suitable. We recommend: AUMA cable set LSW1.
SGR 12.1 Electrical connection AM 01.1 If the AUMA cable set is not used: Use suitable flexible and screened connecting cables. When using connecting cables, e.g. of the heater or switch, requiring direct wiring from the actuator to the XK customer plug (XA-XM-XK, refer to wiring diagram), these connecting cables must be subject to an insulation test in compliance with EN 50178.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Operation Operation Manual operation For purposes of setting and commissioning, in case of motor failure or power failure, the actuator may be operated manually. The handwheel does not rotate during motor operation. Change-over from motor operation to manual operation is not required.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Operation AM 01.1 Figure 17: Local controls Push button for operation command in direction OPEN Push button Stop Push button for operation command in direction CLOSE Selector switch Hot surfaces, e.g. possibly caused by high ambient temperatures or strong direct sunlight! Danger of burns Check surface temperature and wear protective gloves, if required.
Page 23
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Operation Information For actuators equipped with positioner, it is possible to optionally select between open-close duty (REMOTE OPEN-CLOSE) and modulating duty (REMOTE SETPOINT). Selection is made via REMOTE MANUAL input, e.g. based on a 24 V DC signal (refer to wiring diagram).
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Indications AM 01.1 Indications Indication lights The colours of the 3 indication lights on the local controls and the assignment of the signals are specified in the order. Figure 20: Local controls with indication lights (default signalling) illuminated (green): End position OPEN reached illuminated (red): Collective fault signal illuminated (yellow): End position CLOSED reached...
Page 25
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Indications Figure 21: Mechanical position indicator Cover Indicator disc Mark Symbol for position OPEN Symbol for position CLOSED...
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Signals AM 01.1 Signals Feedback signals via output contacts (binary) The output contacts can be used to indicate operation modes of the actuator or the controls as binary signals. The signals are assigned according to the order. Example: Output contact open = end position CLOSED not reached Output contact closed = end position CLOSED reached Switches: 1 NC and 1 NO (standard)
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Commissioning (basic settings) Commissioning (basic settings) Set selector switch to position 0 (OFF). Information: The selector switch is not a mains switch. When positioned to 0 (OFF), the actuator cannot be operated. The controls' power supply is maintained.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Commissioning (basic settings) AM 01.1 Exposed, rotating parts (discs/balls) at the valve! Pinching and damage by valve or actuator. End stops may be set by suitably qualified personnel only. Set end stops to ensure that they are NOT reached during normal operation. Information The setting sequence depends on the valve: Recommendations for butterfly valves: Set end position CLOSED first.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Commissioning (basic settings) 9.2.2 End stop OPEN: set Figure 25: End stop Screws End stop nut Protective cap If the four screws [1] are fastened: Unfasten the screws [1] with approx. 3 turns. Move valve to end position OPEN with handwheel.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Commissioning (basic settings) AM 01.1 9.3.1 Swing angle: modify Figure 27: End stop Grub screw End stop nut Protective cap Travelling nut Sealing ring Unfasten protective cap [3]. While holding end stop nut [2] in position with open end spanner, unfasten grub screw [1].
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Commissioning (basic settings) Loosen screws [2] and remove cover [1] from the switch compartment. Figure 28: If indicator disc [3] is available: Remove indicator disc [3] using a spanner (as lever). Information: To avoid damage to paint finish, use spanner in combination with soft object, e.g.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Commissioning (basic settings) AM 01.1 Figure 30: Torque switching heads Torque switching head black in direction CLOSE Torque switching head white in direction OPEN Lock screws Torque dials Loosen both lock screws [3] at the indicator disc. Turn torque dial [4] to set the required torque (1 da Nm = 10 Nm).
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Commissioning (basic settings) To prevent that the end stop is reached (due to overrun) before the limit switch has tripped, turn handwheel 4 turns (overrun) in the opposite direction. Press down and turn setting spindle [1] with screw driver in direction of the arrow and observe the pointer [2]: While a ratchet click is felt and heard, the pointer [2] moves 90°...
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Commissioning (basic settings) AM 01.1 9.7.1 Running direction CLOSE (black section): set Move valve in direction CLOSE to desired intermediate position. If you override the tripping point inadvertently: Turn valve in opposite direction and approach intermediate position again in direction CLOSE.
"collective fault signal" on the local con- trols. Turn selector switch to position Reset. The fault signal is reset if the device is working properly. If no fault signal is initiated: Request AUMA service to check both wiring and selector switch.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Commissioning (basic settings) AM 01.1 Potentiometer setting — Option — The potentiometer as travel sensor records the valve position. Information This setting is only required if the potentiometer is directly wired to the customer connection XK (refer to wiring diagram).
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Commissioning (basic settings) Figure 39: View of control unit Potentiometer (travel sensor) Potentiometer min. (0/4 mA) Potentiometer max. (20 mA) Measuring point (+) 0/4 20 mA Measuring point ( ) 0/4 20 mA Connect voltage to electronic position transmitter.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Commissioning (basic settings) AM 01.1 Hold lower indicator disc in position and turn upper disc with symbol (OPEN) until it is in alignment with the mark on the cover. Move valve to end position CLOSED again. Check settings: If the symbol (CLOSED) is no longer in alignment with mark...
Page 39
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Commissioning (basic settings) Figure 43: Part-turn actuator with 1-ph AC motor Motor cover Potentiometer Hazardous voltage! Risk of electric shock. Disconnect device from the mains before opening. Danger of corrosion due to damage to paint finish! Touch up damage to paint finish after work on the device.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Commissioning controls settings AM 01.1 Commissioning controls settings The controls are set in the factory according to the order. The settings only have to be changed if the device is used for applications other than those specified in the order.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Commissioning controls settings The limit seating is used to signal that the limit switching will trip shortly before reaching the set tripping torque. If this is not the case, either the indication light on the local controls or the alarm contact K9 (collective fault signal) will signal a fault.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Commissioning controls settings AM 01.1 Information If the controls are equipped with a positioner, switches 1 and 2 (operation commands from remote) must be in position OFF (push-to-run operation). 10.4 Running indication (blinker transmitter): activate/deactivate —...
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Commissioning controls settings Prior to positioner setting, set limit and torque switching as well as potentiometer or electronic position transmitter. 10.6.1 Input ranges (signal type) for setpoint and actual value The input range (signal type) for setpoint E1 and actuator value E2 is set in the factory and marked with a label on the cover plate of the positioner.
Page 44
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Commissioning controls settings AM 01.1 The following reactions are possible: Actuator stops immediately and remains in this position. Fail as is: Fail close: Actuator moves the valve to end position CLOSED. Fail open: Actuator moves the valve to end position OPEN.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Commissioning controls settings 10.6.3 Adjustment in end positions The setting described below applies to the standard positioner version, i.e. maximum setpoint E1 (20 mA) triggers a travel to end position OPEN, minimum setpoint (0/4 mA) triggers a travel to end position CLOSED.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Commissioning controls settings AM 01.1 Adjust positioner using potentiometer 0 [P3]. 9.1 If both LEDs are OFF or the green LED [V28] is illuminated: Turn potentio- meter 0 [P3] slightly clockwise until the yellow LED [V27] is illuminated. 9.2 If the yellow LED [V27] is illuminated: Turn potentiometer 0 [P3] counter- clockwise until the yellow LED [V27] goes out.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Commissioning controls settings Default value: 2.5 % Setting range: 0.5 % to 2.5 % (of the maximum setpoint E1) The dead time prevents the operation to a new setpoint within a pre-determined time Dead time (0.5 to 10 seconds).
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Commissioning controls settings AM 01.1 Disable EMERGENCY Figure 54:Interface board for available option EMERGENCY - OPEN/EMERGENCY command - CLOSE [B1] Link available: EMERGENCY - CLOSE [B2] Link available: EMERGENCY - OPEN Remove face plate. Disconnect links [B1] or [B2].
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Corrective action Corrective action 11.1 Faults during commissioning Table 11: Faults during commissioning Fault description Possible causes Remedy Fault in end position The overrun was not considered when setting Determine overrun: Overrun = travel covered Actuator runs to end stop alt- the limit switching.
Local controls Signal and control board Power supply unit Primary fuses on power supply unit F1/F2 G fuses F1/F2 AUMA Art. no.: Size 6.3 x 32 mm Reversing contactors 1 A T; 500 V K002.277 Power supply≤ 500 V Reversing contactors 2 A FF;...
Page 51
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Corrective action winding. The thermoswitch is tripped as soon as the max. permissible winding temperature has been reached. The actuator is stopped and the red indication light on the local controls is illuminated. The motor has to cool down before the operation can be resumed.
Only perform servicing and maintenance tasks when the device is switched off. AUMA AUMA offer extensive service such as servicing and maintenance as well as customer Service & Support product training. For the relevant contact addresses, please refer to <Addresses>...
The following technical data includes standard and optional features. For detailed information on the customer-specific version, refer to the order-relevant data sheet. This data sheet can be downloaded from the Internet at http://www.auma.com in German and English (indication of commission number required).
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Technical data AM 01.1 Technical data for limit and torque switches Mechanical lifetime 2 x 10 starts Silver plated contacts: U min. 30 V AC/DC U max. 250 V AC/DC I min. 20 mA I max.
Page 55
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Technical data Control Standard: Control inputs 24 V DC, OPEN - STOP - CLOSE (via opto-isolator, one common), current consumption: approx. 10 mA per input, observe minimum pulse duration for modulating ac- tuators Option: Control inputs 115 V AC, OPEN - STOP - CLOSE - EMERGENCY (via opto-isolator, one...
IP 68 IP 68-DS IP 67-DS According to AUMA definition, enclosure protection IP 68 meets the following requirements: Water depth: Maximum 6 m head of water Duration of continuous immersion in water: maximum of 72 hours Up to 10 operations during flooding Modulating duty is not possible during continuous immersion.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 AM 01.1 Technical data Ambient temperature Refer to name plate Standard: 25 °C to +70 °C Options: 40 °C to +70 °C 50 °C to +70 °C Low temperature versions incl. heating system for connection to external power supply 230 V AC or 115 V AC.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Spare parts AM 01.1 Spare parts 14.1 Part-turn actuators SG 05.1 SG 12.1/SGR 05.1 SGR 12.1...
Page 59
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation.
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Spare parts AM 01.1 14.2 Actuator controls AUMA MATIC AM 01.1/AM 02.1...
Page 61
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation.
Page 68
AUMA Riester GmbH & Co. KG P.O.Box 1362 D 79373 Muellheim Tel +49 7631 809 - 0 Fax +49 7631 809 - 1250 riester@auma.com www.auma.com Y000.238/003/en/1.13 For detailed information on AUMA products refer to the Internet: www.auma.com...
Need help?
Do you have a question about the SG 05.1-F05 and is the answer not in the manual?
Questions and answers