Torque Switching: Set - AUMA SG Series Operation Instructions Manual

Part-turn actuators with actuator controls mec 03.1 marine version
Table of Contents

Advertisement

Basic settings for the actuator controls
Limit
Torque
8.4.

Torque switching: set

30
Figure 28: Switches for type of seating
[S9]
End position OPEN
[S10] End position CLOSED
Table 8:
Function of switches [S9], [S10]
ON
Limit seating, sliding switch at white dot
OFF
Torque seating
Setting via software parameters (AUMA CDT)
Condition: Switch [S5] is in position ON (software mode).
Setting parameters
Customer settings
Type of seating
End position CLOSED
End position OPEN
Default value: Limit
Setting values:
Limit seating in end positions.
Torque seating in end positions.
Valve damage due to excessive tripping torque limit setting!
The tripping torque must suit the valve.
Only change the setting with the consent of the valve manufacturer.
Once the set tripping torque is reached, the controls automatically switch off the
actuator (overload protection of the valve).
Setting via switches
Condition: Switch [S5] is in position OFF (hardware mode).
SG 04.2
SG 10.2
with actuator controls MEC 03.1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sg 04.2Sg 05.2Sg 07.2Sg 10.2

Table of Contents