Technical data
Features and functions of actuator controls
Mains voltage, mains frequency
External supply of the electronics
(option)
Overvoltage category
Power electronics
Control
(input signals)
Status signals
(output signals)
Voltage output
46
Standard voltages:
1-phase AC current
Voltages/frequencies
Volt
Hz
Permissible variation of mains voltage: ±10 %
Permissible variation of mains frequency: ±5 %
For current consumption, current type, mains voltage and frequency, refer to the name plate
24 V DC +20 %/ 15 %
Current consumption: With options up to 200 mA
Category III according to IEC 60364-4-443
Power electronics with integral motor controller
Maximum 4 digital inputs (via opto-isolator)
-
Control voltage 24 V DC, current consumption: approx. 15 mA per input
-
Minimum pulse duration for shortest operation pulse: 10 ms.
-
3 inputs on the same potential
-
1 input galvanically isolated
Assignment for open-close actuators:
-
OPEN, STOP, CLOSE (standard)
-
OPEN, STOP, CLOSE, EMERGENCY (option)
-
OPEN, STOP, CLOSE, MODE in combination with positioner (option)
Assignment for modulating actuators:
-
OPEN, STOP, CLOSE, MODE (standard)
Analogue input 0/4
20 mA (galvanically isolated)
Used as input signal for E1 position setpoint (in combination with positioner) or as input signal for
E3 motor speed.
Up to 4 programmable semi-conductors or relay outputs are available, each with max. 30 V/1 A switching
power. They are preassigned with the signals as indicated below.
Variants of semi-conductor output type:
Standard:
4 outputs as NO with 19-pole signal connector:
Compatible with SG .2/SV .2 actuators
1 and 2 at one common, 3 and 4 respectively galvanically isolated
Assignment: CLOSE, OPEN, fault, REMOTE
Option:
4 outputs as NO with 19-pole signal connector: Compatible with SG .2/SV .2 actuators
1, 2 and 3 at one common, 4 galvanically isolated
Assignment: CLOSE, OPEN, fault, REMOTE
Variants of relay output type:
Standard:
3 outputs as NO/NC (change-over contact) with 17-pole signal connector:
Compatible with MEC 02.1 actuator controls
All on the same potential
Assignment: OPEN, CLOSE, fault
Options:
3 outputs as NO with 19-pole signal connector:
All on the same potential
Assignment: OPEN, CLOSE, fault
Assignment (option): OPEN, CLOSE, system OK
4 outputs as NO with 19-pole signal connector:
1, 2 and 3 at one common, 4 galvanically isolated
Assignment: CLOSE, OPEN, fault, REMOTE
4 outputs as NC with 19-pole signal connector:
1, 2 and 3 at one common, 4 galvanically isolated
Assignment: CLOSE, OPEN, fault, REMOTE
Auxiliary voltage 24 V DC, max. 40 mA for supply of control inputs, galvanically isolated from internal
voltage supply
Not available for "external electronics supply" option.
with actuator controls MEC 03.1
115
50/60
SG 04.2
SG 10.2
230
50/60

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sg 04.2Sg 05.2Sg 07.2Sg 10.2

Table of Contents