Basic settings for the actuator controls
32
Setting via switches
Switch [S8] is used to change the motor speed and thus the actuator operating time.
The preset operating time is valid for both operation modes (Local and Remote).
Condition: Switch [S5] is in position OFF (hardware mode).
Figure 30: Switch for operating time
[S8]
Operating time
Default value: depending on the order
Setting range: 9 steps (refer to table)
Table 10:
Switch [S8]
Step
1
2
3
4
5
6
7
8
9
0
1)
Motor is operating in stepping mode
Setting via software parameters (AUMA CDT)
Motor speed and thus actuator operating time can be modified by means of the
software parameters described below. Contrary to operating time setting using switch
[S8], setting via software parameters offers the following additional possibilities:
Different motor speeds for operation modes Local and Remote
Adjustable motor speed setting (operating times)
Setting the motor speed setting (target speed) for operation mode Remote by
an external signal (4
Setting parameters
Condition: Switch [S5] is in position ON (software mode).
Device configuration
with actuator controls MEC 03.1
Operating times for 90° in [s]
SG 04.2/05.2/07.2
1)
63
1)
45
1)
32
22
16
11
8
5.6
4
impermissible switch position
20 mA) or via the analogue input AIN 1
SG 04.2
SG 10.2
SG 10.2
1)
90
1)
63
1)
45
32
22
16
11
8
5.6