Part-turn actuators
SGExC 05.1
SGExC 12.1
Control unit: electronic (MWG)
with actuator controls
AUMATIC ACExC 01.1 Non-Intrusive
Control
Parallel
Profibus DP
Modbus
DeviceNet
Foundation Fieldbus
Operation instructions
Assembly, operation, commissioning

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SGExC 05.1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for AUMA SGExC 05.1

  • Page 1 Part-turn actuators SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) with actuator controls AUMATIC ACExC 01.1 Non-Intrusive Control Parallel Profibus DP Modbus DeviceNet Foundation Fieldbus Operation instructions Assembly, operation, commissioning...
  • Page 2: Table Of Contents

    This document contains information for installation, commissioning, operation and maintenance staff. It is intended to support device installation and commissioning. Reference documents: Manual (Operation and setting) AUMATIC AC 01.1/ACExC 01.1 Parallel Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA (refer to <Addresses>). Table of contents Page Safety instructions.........................
  • Page 3 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Table of contents 5.4.3 Protection cover Operation..........................6.1. Manual operation 6.1.1 Manual operation: engage 6.1.2 Manual operation: disengage 6.2. Motor operation 6.2.1 Local operation 6.2.2 Operation from REMOTE 6.3.
  • Page 4 Service conditions 12.4. Accessories 12.5. Further information Spare parts..........................13.1. Part-turn actuators SGExC 05.1 SGExC 12.1 via plug/socket connector with screw-type terminals (KP, KPH) 13.2. Actuator controls AUMATIC ACExC 01.1 via plug/socket connector with screw-type terminals (KP, KPH) 13.3. Actuator controls AUMATIC ACExC 01.1 with plug/socket connector and terminal blocks (KES) Certificates..........................
  • Page 5: Safety Instructions

    To ensure safe device operation, the maintenance instructions included in this manual Maintenance must be observed. Any device modification requires prior consent of the manufacturer. Range of application AUMA part-turn actuators are designed for the operation of industrial valves, e.g. butterfly valves and ball valves.
  • Page 6: Warnings And Notes

    1, 2, 21, and 22. If temperatures >40 °C are to be expected at the valve mounting flange or the valve stem (e.g. due to hot media), please consult AUMA. Temperatures > 40 °C are not considered with regards to the non-electrical explosion protection.
  • Page 7: References And Symbols

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Safety instructions The signal word (here: DANGER) indicates the level of hazard. References and symbols The following references and symbols are used in these instructions: Information The term Information preceding the text indicates important notes and information.
  • Page 8: Identification

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Identification ACExC 01.1 Non-Intrusive Identification Name plate Each device component (actuator, controls, motor) is equipped with a name plate. Figure 1: Arrangement of name plates Actuator name plate Controls name plate Motor name plate Additional plate, e.g.
  • Page 9: Short Description

    A part-turn actuator is an actuator which transmits a torque to the valve for less than one full revolution. It need not be capable of withstanding thrust. AUMA part-turn actuators are driven by an electric motor. A handwheel is provided for manual operation. Switching off in end positions may be either by limit or torque seating.
  • Page 10 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Identification ACExC 01.1 Non-Intrusive Intrusive version (control unit: electromechanical): Intrusive - Non-Intrusive Limit and torque setting is performed via switches in the actuator. Non-Intrusive version (control unit: electronic): Limit and torque setting is performed via the controls, actuator and controls housings do not have to be opened.
  • Page 11: Transport, Storage And Packaging

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Transport, storage and packaging Transport, storage and packaging Transport For transport to place of installation, use sturdy packaging. Hovering load! Risk of death or serious injury. Do NOT stand below hovering load.
  • Page 12: Assembly

    ACExC 01.1 Non-Intrusive Assembly Mounting position AUMA actuators and actuator controls can be operated without restriction in any mounting position. Ball handle: fit to handwheel To avoid damage during transport, the ball handle is fitted at the rear of the handwheel.
  • Page 13: Coupling

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Assembly 4.3.1 Coupling Figure 7: Coupling fitting dimensions Coupling Valve shaft Grub screw Screw Table 1: Coupling fitting dimensions Type, size - mounting flange X max [mm] Y max [mm] Z max [mm] SGExC 05.1-F05...
  • Page 14: Mounting Positions Of Local Controls

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Assembly ACExC 01.1 Non-Intrusive Fasten actuator with screws [4]. Information: We recommend glueing the screws using sealing material to avoid contact corrosion. Fasten screws [4] crosswise with a torque according to table:...
  • Page 15: Mounting Positions: Modify

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Assembly 4.4.1 Mounting positions: modify Flameproof enclosure, danger of explosion! Risk of death or serious injury. Before opening, ensure that there is no explosive gas and no voltage. Handle cover and housing parts with care.
  • Page 16: Electrical Connection

    The pertaining wiring diagram/terminal plan (in German and English language) is plan attached to the device in a weather-proof bag, together with these operation instructions. It can also be obtained from AUMA (state commission no., refer to name plate) or downloaded directly from the Internet (www.auma.com). Protection on site For short-circuit protection and for disconnecting the actuator from the mains, fuses and disconnect switches have to be provided by the customer.
  • Page 17: Connecting Via Plug/Socket Connector With Screw-Type Terminals (Kp, Kph)

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Electrical connection The interference immunity of signal and bus cables increases if the cables are laid close to the earth potential. If possible, avoid laying long cables and make sure that they are installed in areas being subject to low interference.
  • Page 18: Cable Connection

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Electrical connection ACExC 01.1 Non-Intrusive Hazardous voltage! Risk of electric shock. Disconnect device from the mains before opening. Loosen screws [2] and remove cover [1]. Terminal compartment [4] is designed for explosion protection Ex e (increased safety).
  • Page 19: Terminal Compartment: Close

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Electrical connection In case of a fault: Hazardous voltage while protective earth conductor is NOT connected! Risk of electric shock. Connect all protective earth conductors. Connect PE connection to external protective earth conductor of connecting cables.
  • Page 20: Connecting Via Plug/Socket Connector With Terminal Blocks (Kes)

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Electrical connection ACExC 01.1 Non-Intrusive Clean sealing faces of cover [1] and housing. Check whether O-ring [3] is in good condition, replace if damaged. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and insert it correctly.
  • Page 21: Cable Connection

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Electrical connection Seal cable entries which are not used with approved plugs suitable for the re- quired protection type. Remove cable sheathing and insert the wires into the cable glands.
  • Page 22: Terminal Compartment: Close

    In case of heavy vibration of the valve. Design Permissible length of connecting cables: max. 100 m. Observe prior to Permissible length of connecting cables for later separation of actuator and connection controls: max. 10 m. We recommend: AUMA cable sets LSW21-KES or LSW22-KP.
  • Page 23: Parking Frame

    SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Electrical connection If the AUMA cable set is not used: Use suitable flexible and screened connecting cables. Use separate CAN bus cable of 120 Ohm character impedance for MWG (e.g. UNITRONIC BUS-FD P CAN UL/CSA - 2 x 2 x 0.5 mm², manufacturer: Lapp).
  • Page 24: Operation

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Operation ACExC 01.1 Non-Intrusive Operation Manual operation For purposes of setting and commissioning, in case of motor failure or power failure, the actuator may be operated manually. The handwheel does not rotate during motor operation. Change-over from motor operation to manual operation is not required.
  • Page 25: Operation From Remote

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Operation Figure 22: Local controls Push button OPEN Push button STOP Push button CLOSE Push button Reset Selector switch Indication lights/LEDs Hot surfaces, e.g. possibly caused by high ambient temperatures or strong...
  • Page 26: Menu Navigation Via Push Buttons (For Settings And Indications)

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Operation ACExC 01.1 Non-Intrusive Information For actuators equipped with a positioner, it is possible to select between open-close control (Remote OPEN-CLOSE) and setpoint control (remote SETPOINT). Selec- tion is made via MODE input, e.g. based on a 24 V DC signal (refer to wiring diagram).
  • Page 27: Password Entry

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Operation Group = Status indications Group = Menu (settings) Group = Diagnostic indications The active group is displayed in the top right corner of the display. Change from group...
  • Page 28: Language Change In The Display

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Operation ACExC 01.1 Non-Intrusive Language change in the display Via the menu to parameter: MAIN MENU (M0) LANGUAGE/CONTRAS (M00) VIEW (M00) EDIT (M01) LANGUAGE (M010) Default value: ENGLISH Setting range: ENGLISH, GERMAN, MAGYAR, POLSKI, TUERKCE,...
  • Page 29 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Operation Enter password: Press 4 x = 0000 (default factory password). Display indicates: EDIT M010 LANGUAGE LCD CONTRAST Press Display shows the set value: EDIT M010 LANGUAGE ENGLISH :EDIT C:ESC Press again to enter the edit mode.
  • Page 30: Indications

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Indications ACExC 01.1 Non-Intrusive Indications Status indications in the display The status indications in the display locally indicate the current operation states as well as faults and warnings. This section describes the indications for the operation states. Faults and warnings are described in the <Fault indications and warning indications>...
  • Page 31: Status Indication S4 - Torque

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Indications End position OPEN reached. CLOSED POSITION End position CLOSED reached. SETPOINT POSITION Setpoint (modulating actuators only). 7.1.2 Status indication S4 - torque A deflection to the left side indicates torque in direction CLOSE.
  • Page 32: Mechanical Position Indicator/Running Indication

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Indications ACExC 01.1 Non-Intrusive Figure 30: Indication lights/LEDs on local controls Marking with symbols (standard) Marking with figures (option) Table 7: Meaning of signals Indication light Behaviour (default) Meaning of signal illuminated...
  • Page 33: Signals

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Signals Signals Feedback signals via output contacts (binary) The output contacts can be used to indicate operation modes of the actuator or the controls as binary signals. The signals can be freely assigned. Example:...
  • Page 34: Commissioning (Basic Settings)

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Commissioning (basic settings) ACExC 01.1 Non-Intrusive Commissioning (basic settings) Set selector switch to position 0 (OFF). Information: The selector switch is not a mains switch. When positioned to 0 (OFF), the actuator cannot be operated. The controls' power supply is maintained.
  • Page 35: End Stop Closed: Set

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Commissioning (basic settings) Exposed, rotating parts (discs/balls) at the valve! Pinching and damage by valve or actuator. End stops may be set by suitably qualified personnel only. Set end stops to ensure that they are NOT reached during normal operation.
  • Page 36: End Stop Open: Set

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Commissioning (basic settings) ACExC 01.1 Non-Intrusive 9.2.2 End stop OPEN: set Figure 35: End stop Screws End stop nut Protective cap If the four screws [1] are fastened: Unfasten the screws [1] with approx. 3 turns.
  • Page 37: Swing Angle: Modify

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Commissioning (basic settings) 9.3.1 Swing angle: modify Figure 37: End stop Grub screw End stop nut Protective cap Travelling nut Sealing ring Unfasten protective cap [3]. While holding end stop nut [2] in position with open end spanner, unfasten grub screw [1].
  • Page 38: Type Of Seating: Check/Edit For End Positions

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Commissioning (basic settings) ACExC 01.1 Non-Intrusive Type of seating: check/edit for end positions Valve damage due to incorrect setting! The torque must suit the valve. Only change the setting with the consent of the valve manufacturer.
  • Page 39 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Commissioning (basic settings) Press . Display indicates: SETTINGS SET LIMIT SWITCHES SEATING MODE TORQUE Press Display indicates: SEATING MODE M110 VIEW EDIT to select between VIEW EDIT View or edit? Display seating mode: continue with 8.
  • Page 40 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Commissioning (basic settings) ACExC 01.1 Non-Intrusive 11. Press . Change seating mode: Display indicates: SEATING MODE M111 VIEW EDIT 12. Press Display indicates: ENTER PASSWORD 0 * * * :EDIT C:ESC 13. Enter password: Press 4 x = 0000 (default factory password).
  • Page 41: Torque Switching: Check/Set

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Commissioning (basic settings) 15. Press again to enter the edit mode. Display indicates: EDIT M1110 OPEN POSITION LIMIT :EDIT C:ESC EDIT M1111 CLOSED POSITION LIMIT :EDIT C:ESC 16. Set new value: Press 17.
  • Page 42 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Commissioning (basic settings) ACExC 01.1 Non-Intrusive Default value: according to order data Setting range: according to torque setting range, refer to actuator name plate Step by step: Set selector switch to position 0 (OFF).
  • Page 43 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Commissioning (basic settings) View or edit? Display torque setting: continue with 8. Edit torque setting: continue with 11. Display torque setting: Press Display indicates: VIEW M1200 OPENING CLOSING BY-PASS DURATION...
  • Page 44 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Commissioning (basic settings) ACExC 01.1 Non-Intrusive 13. Enter password: Press 4 x = 0000 (default factory password). EDIT M1210 OPENING CLOSING BY-PASS DURATION EDIT M2111 OPENING CLOSING BY-PASS DURATION to select between...
  • Page 45: Limit Switching: Set

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Commissioning (basic settings) 17. Accept value or cancel? Accept value: Press Cancel process without accepting the value: Press Display indicates: EDIT M1210 OPENING 100% :EDIT C:ESC EDIT M1211 CLOSING...
  • Page 46 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Commissioning (basic settings) ACExC 01.1 Non-Intrusive Press and hold it down for approx. 3 seconds. Display indicates: MAIN MENU LANGUAGE/CONTRAST SETTINGS OPERATIONAL DATA Press . Display indicates: MAIN MENU LANGUAGE/CONTRAST SETTINGS OPERATIONAL DATA...
  • Page 47 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Commissioning (basic settings) Press to enter the edit mode. Set end position CLO- Display indicates: SET LIMIT SWITC M100 CLOSED POSITION :ACCEPT C:ESC Engage manual operation. 10. Turn handwheel until valve is closed.
  • Page 48: Test Run

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Commissioning (basic settings) ACExC 01.1 Non-Intrusive 18. Return to status display: Press several times until is displayed. Information: If an end position cannot be set: Check the type of control unit in actuator.
  • Page 49: Switch Compartment: Open

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Commissioning (basic settings) Operate actuator using push buttons OPEN - STOP - CLOSE. The limit switching is set correctly if (default indication): The yellow indication light/LED1 is illuminated in end position CLOSED The green indication light/LED5 is illuminated in end position OPEN The indication lights go out after travelling into opposite direction.
  • Page 50: Switch Compartment: Close

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Commissioning (basic settings) ACExC 01.1 Non-Intrusive Move actuator to end position OPEN. Hold lower indicator disc in position and turn upper disc with symbol (OPEN) until it is in alignment with the mark on the cover.
  • Page 51 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Commissioning (basic settings) Table 8: Operating time setting for 90° Size Operating times SGExC 05.1 4 to 32 seconds SGExC 07.1 8 to 63 seconds SGExC 10.1 16 to 125 seconds SGExC 12.1...
  • Page 52: Corrective Action

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Corrective action ACExC 01.1 Non-Intrusive Corrective action 10.1 Faults during commissioning Table 9: Faults during commissioning Fault description Possible causes Remedy Fault in end position The overrun was not considered when setting...
  • Page 53: Status Indication S2 - Warnings

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Corrective action FAULT IND. NO FAULT Table 11: Description of the fault indications Signal Description Remedy NO FAULT No fault has occurred. INTERNAL FAULT Internal fault has occurred. For further information:...
  • Page 54: Status Indication S3 - Causes For Not Ready Remote

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Corrective action ACExC 01.1 Non-Intrusive Signal Description Remedy WARNING STARTS/RUN Preset values for max. starts/h or max. run- Check modulating behaviour. ning time/h have been exceeded. Increase dead time. Reduce number of setpoint changes.
  • Page 55: Motor Protection (Thermal Monitoring)

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Corrective action Figure 51: Access to fuses Rear cover Electrical connection F1/F2 Primary fuses on power supply unit G fuses F1/F2 AUMA Art. No.: Size 6.3 x 32 mm Reversing contactors 1 A T;...
  • Page 56 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Corrective action ACExC 01.1 Non-Intrusive For further information to this topic, please refer to the Manual (Operation and setting).
  • Page 57: Servicing And Maintenance

    Only perform servicing and maintenance tasks when the device is switched off. AUMA AUMA offer extensive service such as servicing and maintenance as well as customer Service & Support product training. For the relevant contact addresses, please refer to <Addresses>...
  • Page 58: Maintenance

    Loosen the screws [2]. Remove plug/socket connector. Hereby, cover [1] and terminal board [5] or frame [6] remain together. Seal open plug/socket connection, e.g. using AUMA protection cover and parking frame. Fitting the plug: Clean sealing faces at the cover and the housing.
  • Page 59: Disposal And Recycling

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Servicing and maintenance Take care of possible discolouration of the terminals and wires. This would in- dicate an increased temperature. For Ex housings, pay special attention to a possible collection of water. This may originate from “breathing”...
  • Page 60: Technical Data

    The following technical data includes standard and optional features. For detailed information on the customer-specific version, refer to the order-relevant data sheet. This data sheet can be downloaded from the Internet at http://www.auma.com in German and English (indication of commission number required).
  • Page 61: Features And Functions Of Actuator Controls

    Reversing contactors (mechanically and electrically interlocked) for motor power up to power class A1 Options: Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators) for AUMA power class B1 Control Standard: Control inputs 24 V DC, OPEN - STOP - CLOSE - EMERGENCY (via opto-isolator, one common), current consumption: Approx.
  • Page 62 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Technical data ACExC 01.1 Non-Intrusive Functions Standard: Switch-off mode adjustable Limit or torque seating for end position OPEN and end position CLOSED Torque monitoring over the whole travel Torque by-pass, adjustable up to 5 seconds (no torque monitoring during this time)
  • Page 63: Service Conditions

    IP 67 Options: IP 68 According to AUMA definition, enclosure protection IP 68 meets the following requirements: Water depth: Maximum 6 m head of water Duration of continuous immersion in water: maximum of 72 hours Up to 10 operations during flooding Modulating duty is not possible during continuous immersion.
  • Page 64: Accessories

    Within actuator controls: pollution degree 2 Outside actuator controls (in closed condition): pollution degree 4 Finish coating Standard: Two-component iron-mica coating Colour Standard: AUMA silver-grey (similar to RAL 7037) Ambient temperature Refer to name plate Standard: 40 °C to +40 °C Options: 50 °C to +40 °C...
  • Page 65: Spare Parts

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Spare parts Spare parts 13.1 Part-turn actuators SGExC 05.1 SGExC 12.1 via plug/socket connector with screw-type terminals (KP, KPH)
  • Page 66 Information: Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation.
  • Page 67: Actuator Controls Aumatic Acexc 01.1 Via Plug/Socket Connector With Screw-Type Terminals

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Spare parts 13.2 Actuator controls AUMATIC ACExC 01.1 via plug/socket connector with screw-type terminals (KP, KPH)
  • Page 68 Information: Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation.
  • Page 69: Actuator Controls Aumatic Acexc 01.1 With Plug/Socket Connector And Terminal Blocks

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Spare parts 13.3 Actuator controls AUMATIC ACExC 01.1 with plug/socket connector and terminal blocks (KES)
  • Page 70 Information: Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation.
  • Page 71: Certificates

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Certificates Certificates 14.1 Declaration of Incorporation and EC Declaration of Conformity...
  • Page 72: Atex Certificate

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Certificates ACExC 01.1 Non-Intrusive 14.2 ATEX certificate...
  • Page 73 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Certificates...
  • Page 74 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Certificates ACExC 01.1 Non-Intrusive...
  • Page 75: Index

    SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) ACExC 01.1 Non-Intrusive Index Index LEDs Language in the display Limit switching 45 , 48 ATEX certificate Local control Accessories (electrical Local controls connection) Low temperature version Actuator operation from remo- Lubrication...
  • Page 76 SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) Index ACExC 01.1 Non-Intrusive S0/S6 - operation S4 - torque Safety instructions Safety instructions/warnings Service Service conditions Servicing Short-circuit protection Signals Spare parts Standards Status indications (in the dis- play) Storage Support...
  • Page 77: Addresses

    Auma Endüstri Kontrol Sistemleri Limited UK Clevedon, North Somerset BS21 6TH  irketi Tel +44 1275 871141 TR 06810 Ankara AUMA Riester GmbH & Co. KG Fax +44 1275 875492 Tel+90 312 217 32 88 mail@auma.co.uk Fax+90 312 217 33 88 Plant Müllheim...
  • Page 78 AUMA worldwide Ferrostaal de Colombia Ltda. AUMA Actuators Middle East W.L.L. CO Bogotá D.C. AE 15268 Salmabad 704 Tel +57 1 401 1300 Tel +973 17877377 Fax+57 1 416 5489 Fax +973 17877355 dorian.hernandez@ferrostaal.com Naveen.Shetty@auma.com www.ferrostaal.com PERFECT CONTROLS Ltd. PROCONTIC Procesos y Control HK Tsuen Wan, Kowloon Automático...
  • Page 79 AUMA worldwide...
  • Page 80 AUMA Riester GmbH & Co. KG P.O.Box 1362 D 79373 Muellheim Tel +49 7631 809 - 0 Fax +49 7631 809 - 1250 riester@auma.com www.auma.com Y003.148/003/en/4.12 For detailed information on AUMA products refer to the Internet: www.auma.com...

This manual is also suitable for:

Sgexc 10.1Sgexc 07.1Sgexc 12.1

Table of Contents