Commissioning
7.1.2.
End stop OPEN: set
Information
20
3.
If the valve end position is not reached:
Slightly turn setting screw [4] counterclockwise until valve end position
CLOSED can be correctly set.
Turning the setting screw [4] clockwise decreases the swing angle.
Turning the setting screw [4] counterclockwise increases the swing angle.
4.
Turn setting screw [4] clockwise to the stop.
This completes the setting of end stop CLOSED.
5.
Check O-ring in screw plug [3] and replace if damaged.
6.
Fasten and tighten screw plug [3].
Once this procedure is complete, the end position detection for end position CLOSED
can be set immediately.
In general, the end stop OPEN does not have to be set.
1.
Remove screw plug [1].
2.
Move valve to end position OPEN with crank handle/handwheel.
3.
If the valve end position is not reached:
Slightly turn setting screw [2] counterclockwise until valve end position
OPEN can be correctly set.
Turning the setting screw [2] clockwise decreases the swing angle.
Turning the setting screw [2] counterclockwise increases the swing angle.
4.
Turn setting screw [2] clockwise to the stop.
This completes the setting of end stop OPEN.
5.
Check O-ring in screw plug [1] and replace if damaged.
6.
Fasten and tighten screw plug [1].
Once this procedure is complete, the end position detection for end position OPEN
can be set immediately.
SG 04.2
SG 10.2
with actuator controls MEC 03.1