8800 Series Chassis Switch Hardware Installation Guide
Securing the Rack
The rack should be attached to the wiring closet floor with 3/8-inch (9.5 mm) lag screws or
equivalent hardware. The floor under the rack should be level within 3/16-inch (5 mm). Use a
floor-leveling cement compound if necessary or bolt the racks to the floor as shown in the
following figure.
Figure 12. Correctly secured rack
Brace open equipment racks if the channel thickness is less than 1/4 inch (6.4 mm).
Cable Requirements
This section describes requirements for the cable you should use when installing your
network equipment. It includes:
•
Cabling Standards
•
Cable Labeling and Record Keeping
•
Selecting Cable
•
Installing Cable
•
Radio Frequency Interference
Cabling Standards
NETGEAR recommends using the Building Industry Consulting Service International (BICSI)
Registered Communications Distribution Designer (RCDD), which is globally recognized as a
standard in site planning and cabling. For information, go to:
http://www.bicsi.org
on page 33
on page 34
on page 34
on page 36
on page 38
Chapter 4. Site Preparation
| 33