FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Alarm ID
0x5023
0x502A
0x502B
0x502C
0x5033
0x5034
0x5035
0x503C
0x5043
0x5044
0x5051
Issue 01 (2019-03-05)
Alarm
Alarm
Name
severity
L3
Critical
overloaded
Upper L1
Major
current
threshold
exceeded
Upper L2
Major
current
threshold
exceeded
Upper L3
Major
current
threshold
exceeded
Lower L1
Message
current
threshold not
reached
Lower L2
Message
current
threshold not
reached
Lower L3
Message
current
threshold not
reached
Main
Message
three-phase
current
unbalanced
Main THDu
Message
high
Main THDi
Message
high
Current
Major
transformer
cable
connected
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Solution
Cause
The L3 current
Check the power of all
exceeds the
output loads.
threshold.
The L1 current
Check the power of all
exceeds the
output loads.
threshold.
The L2 current
Check the power of all
exceeds the
output loads.
threshold.
The L3 current
Check the power of all
exceeds the
output loads.
threshold.
The L1 current
Check the power of all
exceeds the
output loads.
threshold.
The L2 current
Check the power of all
exceeds the
output loads.
threshold.
The L3 current
Check the power of all
exceeds the
output loads.
threshold.
The imbalance
Check the power of all
among the L1,
output loads and adjust
L2, and L3
the loads until the three
phase current
phase currents are
exceeds the
almost the same.
threshold.
The THDu on
Check the power input.
the main circuit
exceeds the
threshold.
The THDi on
Check the power input.
the main circuit
exceeds the
threshold.
The cable to
Check the cable
the current
connection.
transformer on
the input board
3 Alarm Reference