Huawei FusionModule5000 Maintenance Manual page 69

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
0036
-2
0037
-1
0040
-7
Issue 01 (2019-03-05)
Alarm
Sever
System Action
Name
ity
on
addition, the
discharger
cannot be
started. If the
mains is
abnormal, the
system will
transfer to
bypass mode or
shut down
based on logic.
Battery
Warni
None.
mainte
ng
nance
remind
er
Battery
Critic
The system exits
underv
al
from battery mode
oltage
and transfers to a
working mode
based on logic.
1. The system
Rectifi
Critic
shuts down the
er
al
module.
abnorm
al
2. If only one
module is
working, or the
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
threshold.
The
configured
3. Check that the
number of
batteries is
less than the
actual number.
The actual
number of
batteries does
not meet
requirements.
The time for
Maintain the
maintenance
batteries.
arrives.
1. Check whether
The UPS
works long in
battery mode.
The charger is
2. Check whether
faulty.
3. Check whether
4. Check whether
1. Check that the
The fan for the
power module
is abnormal.
The air
channel of the
2. Check whether
power module
3 Alarm Reference
batteries
matches the
actual number.
actual number of
batteries meets
requirements.
the battery
voltage is
normal.
the output is
overloaded.
any battery is
damaged. If yes,
replace the
battery.
any battery
charger
generates an
alarm. If yes,
replace the
faulty module.
air channel for
the module is
free from
blockage.
61