FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
0530
-1
0032
-1
Issue 01 (2019-03-05)
Alarm
Sever
System Action
Name
ity
Battery
Critic
The system
ground
al
generates alarm
fault
information and
causes the BCB to
trip if the BCB is
ON.
1. The system
Battery
Critic
shuts down the
overvol
al
charger.
tage
protecti
2. Hardware may
be damaged. In
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
1. Check whether
The battery
string is not
properly
grounded.
The battery
ground
monitoring
cable is faulty.
The dry
2. Check whether
contact board
is faulty.
3. If no battery
1. Check the
The battery
voltage is
greater than
2. Check that the
the upper
3 Alarm Reference
related power
module.
the positive and
negative
terminals of the
battery string are
grounded or
have sufficient
resistance to the
ground.
the battery
grounding
failure detector
is faulty by
replacing it with
a new one.
grounding
failure detector
is available,
check on the dry
contact board
whether the
battery
grounding
failure detector
is enabled. If
yes, disable it
and check
whether the
alarm is cleared.
If the alarm
persists, the dry
contact board
may be faulty.
Replace the
board.
battery voltage.
configured
number of
60