Huawei FusionModule5000 Maintenance Manual page 82

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Alarm ID
0x5039
0x503A
0x503B
0x503D
0x503E
0x503F
0x5040
0x5041
Issue 01 (2019-03-05)
Alarm Name
Alarm
severity
reached
Branch 4 lower
Message
current
threshold not
reached
Branch 5 lower
Message
current
threshold not
reached
Branch 6 lower
Message
current
threshold not
reached
Large current
Major
shock on
branch 1
Large current
Major
shock on
branch 2
Large current
Major
shock on
branch 3
Large current
Major
shock on
branch 4
Large current
Major
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Alarm Reference
Possible
Solution
Cause
the threshold.
corresponding
branch.
The current of
Check the
the fourth
power of the
output branch
load on the
exceeds the
corresponding
threshold.
branch.
The current of
Check the
the fifth output
power of the
branch exceeds
load on the
the threshold.
corresponding
branch.
The current of
Check the
the sixth output
power of the
branch exceeds
load on the
the threshold.
corresponding
branch.
The current of
Check that the
the first output
insulation layer
branch exceeds
of the cable to
the threshold.
the
corresponding
output branch is
in good contact.
The current of
Check that the
the second
insulation layer
output branch
of the cable to
exceeds the
the
threshold.
corresponding
output branch is
in good contact.
The current of
Check that the
the third output
insulation layer
branch exceeds
of the cable to
the threshold.
the
corresponding
output branch is
in good contact.
The current of
Check that the
the fourth
insulation layer
output branch
of the cable to
exceeds the
the
threshold.
corresponding
output branch is
in good contact.
The current of
Check that the
74